Anti-Locking Function
Disabled
Enabled
It is possible to enable an automatic valve movement, useful when there are long periods of
inactivity, for example during the summer season. If this function is activated you can select how
long can be the period of inactivity (see parameter "
Anti-Locking Valve movement frequency
"); before that the valve performs a switching ON and after 5 minutes.a switching OFF
Anti-Locking Valve movement frequency
1 day
3 days
10 days
Determines the maximum period of inactivity allowed.
Lock Function
Disabled
Enabled
When lock function is enabled it allows
switching the relay in a defined state and forcing it to
maintain this state even if the it receives 1-bit or 1 byte control commands.
Behaviour on power up
Valve Open
Valve Close
STOP – no movement
On power up it is possible to set the status of each valve with this parameter.
9.3. Lock
Function
When lock function is enabled it allows, as a result of receiving a telegram on the
<Output x> Lock
Function;
to switch the relay in a defined state and force it to maintain this state even if the object
switching value changes. The behaviour of the lock function is the same described in par.
6.11
Lock
Function
.
This function can be enabled or with 1 bit commands than with 1 byte commands.
KNX PARAMETER
SETTINGS
Initial Value for Lock Object
Value “0”
Value “1”
This parameter selects the value of the lock object after a power on; appropriately changing this
value it is possible to start the output channel related to the lock function as “locked” or
“unlocked”. (
See note 1
).
Telegram for Lock Activation
Telegram “0”
Telegram “1”
This parameter selects the values associated to the “lock” or “unlock” condition.
Valve Position when Lock is Active
Valve Open
Valve Close
This parameter selects the state the valve must assume when the “lock function” becomes active”.
(
See note 2
).