9. Output Configuration for motor reduction driver
Outputs can be configured in pairs for the management of motor reductor; up to 4 channels
(Channels A to D):
Channel
Output / Function
Output / Function
CH A
OUT 1 closed
OPEN
OUT 2 closed
CLOSE
CH B
OUT 3 closed
OPEN
OUT 4 closed
CLOSE
CH C
OUT 5 closed
OPEN
OUT 6 closed
CLOSE
CH D
OUT 7 closed
OPEN
OUT 8 closed
CLOSE
Typical wiring scheme:
Communication object scheme:
2 POINT CONTROL OBJECT :
1 bit command to open/close the valve completely.
CONTINUOUS CONTROL OBJECT: 1 byte command (0% -100%) to set the valve position.
LOCK FUNCTION OBJECT:
if enabled, according to the receipt of a 1 bit telegram,
realizes a function for enabling / disabling the opening and
closing of the valve
1 BIT STATUS OBJECT:
send information about the position (open / closed) of the
valve using a 1 bit telegram
1 BYTE STATUS OBJECT:
send information about the proportion of active regulation
using a 1 byte telegram
COUPLED
RELAYS
LOCK FUNCTION
OBJECT
2 POINT CONTROL
OBJECT
CONTINUOUS
CONTROL OBJECT
1 BIT STATUS
OBJECT
1 BYTE STATUS
OBJECT
This configuration can be used to drive a bistable device with motor reductor,
typically a solenoid valve with 3 point control, or a driver for ventilation grilles in
AC systems, etc...
Motor MUST have position limit switches.
M
Common
Open
Close
Position limit switch