KNX PARAMETER
SETTINGS
Send Device ON-LINE
Disabled
Enabled
Device ON-LINE sending time
10 min
1 hr
12 Hr
24 Hr
Through this parameter it’s possible to enable a cyclical sending, on the bus, of a 1 bit telegram
with value “1”; this sending has a programmable time interval.
This message can be used to detect errors like power failure or breakage of the device to a
monitoring system or to a bus control system.
KNX PARAMETER
SETTINGS
All Valve Closed
Disabled
Enabled
All Valve Closed Function depends on;
Electric valves output
Motor reduction Driver Channels
Electric valves output and Motor reduction
Channels
See paragraph 9.4 Function VALVES ALL CLOSED
3.2. Communications
Objects