5.1. Electric
connections
For 4 pipes systems:
Uscita
Descrizione
Collegamento
OUT 1
VALVE HEATING
Connect to heating valve - ON/OFF contact
OUT 2
VALVE COOLING
Connect to cooling valve - ON/OFF contact
OUT 3
FAN COIL SPEED 1
Connect to fan coil speed 1 – ON/OFF contact
OUT 4
FAN COIL SPEED 2
Connect to fan coil speed 2 – ON/OFF contact
OUT 5
FAN COIL SPEED 3
Connect to fan coil speed 3 – ON/OFF contact
For 2 pipes systems:
Uscita
Descrizione
Collegamento
OUT 1
VALVE HEAT/COOL
Connect to heating / cooling valve - ON/OFF contact
OUT 2
-
See note (1)
OUT 3
FAN COIL SPEED 1
Connect to fan coil speed 1 – ON/OFF contact
OUT 4
FAN COIL SPEED 2
Connect to fan coil speed 2 – ON/OFF contact
OUT 5
FAN COIL SPEED 3
Connect to fan coil speed 3 – ON/OFF contact
(1)
When fan coil actuator is configured as 2 pipes system OUT2 is not used; anyway it is
configured to switch in the opposite mode of OUT1. When OUT1 goes ON OUT2 goes OFF and
vice versa. This behaviour can be used to manage systems where the Heating / Cooling hydraulic
system is based on a 3 way valve which switches 2 times a year when passing from Summer to
Winter season and vice versa.
5.2. Control of Heating / Cooling Valve