Position when Lock Ends
Valve Open
Valve Close
Stop – no movement
Same values of command object
Valve Open
“valve open” position.
Valve Close
“valve closed” position.
Stop – no movement
motor remains in the state it is when the lock
was active
Same values of command object the output channel returns to its condition prior
to the activation of the block unless you have
received a telegram on the command object; in
this case, the last command received is
executed.
NOTES:
[1]
: If the parameter “Initial Value for Lock Object” has the same value of “Telegram for Lock
Activation” happens that, on power up, the output channel starts in lock mode, waiting for a
“unlock” telegram in order to become active. Note that, even if the channel starts with lock function
already active it does not go automatically in the position defined by the parameter “Relay
Position when Lock is Active “; because this behaviuor is determined only by the parameter
“Behaviour on power up”
9.4. Function VALVES ALL CLOSED
When at least one output is configured on the device type "Electric Valve Driver" or "Motor
Reduction Driver (Solenoid Actuator)" you can enable a communication object that sends 1 bit
value: telegram “0” - when all the valves are turned off and a telegram “1” when at least one valve
among those the device is controlling is active.
For outputs configured as "Motor Reduction Driver”- the valve is considered closed when the relay
that controls it puts it in closed state (for ON/OFF mode – 1 bit) or when the control value is less
than the minimum control value (Continuous control – parameter: "Lower limit value" - 1 byte);
Vice versa it is considered open when the relay that controls it puts it in open state (for ON/OFF
mode – 1 bit) or when the control value is greater than or equal to the value of the minimum control
value.
When outputs are configured as Electric Driver “with 2-point control ON/OFF", valve is considered
closed when the relay that controls it puts it in a close state and open when the relay puts it in the
open state.