When the scene function is enabled a communication object named
<Output x> Scene
becomes
visible.
It is possible to send to the device two possible commands:
recall scene - is a command to create a specific condition
store scene - is a command to learn and store the current status (at the moment the
command is received) of the contact, and then reproduce it once the recall command is
received
For every channel it is possible to store a maximum of 4 output scene.
KNX PARAMETER
SETTINGS
Scene Number <X>
0 … 64
For the 4 possible scenes, this number is the unique identifier for the scene: valid numbers are
from 0 to 63; 64 means scene is not active.
Initial value Scene <X>
Contact Open
Contact Close
For the 4 possible scene this number allow to initialize the status associated to previously
selected scene number avoiding to execute the store scene procedure. If the store scene is done,
this value is overwritten.
Learn Scene
Enabled
Disabled
This parameter enable / disable the output channel from storing value received from the bus; if
this parameter is set to disable the value associated are set only by the parameters
“Initial value
Scene <X>”
and cannot be modified without a ETS download.
NOTES:
[1]:
When a scene is recalled the output channel behaves in the same way as it would have
received a telegram “0” or “1” on the
<Output x> Relay Command
communication objects; this
means that if a output is normally open with the staircase light timer enabled – the receipt of a
telegram “1” triggers a timed ON with automatic OFF when the timer expires.
[2]:
After a ETS download the device assumes the value of parameter: “
Initial value Scene <X>”
as a value in memory for the corresponding scene and overwrites previous memorized scene
positions.