91
40. Turn OFF Pump(s)
41. Turn OFF Main Power Disconnects (MECHANICAL)
42. Close Motor Starter Box(es) (MECHANICAL)
43. Turn ON Main Power Disconnect (MECHANICAL)
44. Enter F1 Set Up Screen (MECHANICAL)
45. Turn ON Pump(s)
46. Verify and record CHC Chamber gauge Pressure /transducer display
47. Verify and record Separator inlet and outlet pressures/transducer display
48. Verify and record Auto Filter inlet and outlet pressures/transducer display
a.
Verify DP less than 3
49. Record Conductivity controller conductivity reading (AFTER CALIBRATION)
50. Water samples are to be taken from
each
sump and make up source.
a.
The samples are to be shipped to EcoWater CHC.
b.
Each sample must be labeled with the following information:
i. Location
ii. Date
iii. Type Sump (CHC) or Make up
1.
Include the sump number or identifier when multiple sumps are being treated.
51. Water Samples and Biological Testing (MECHANICAL)
a.
Water samples are to be taken from each sump and make up source.
b.
The samples are to be refrigerated and shipped to EcoWater CHC OVERNIGHT for biological
testing
52. Dip Slides are to be taken from each sump sample and results recorded and reported to EcoWater CHC after 48
hours
a.
All results greater than 10,000 need to be photographed and submitted to EcoWater CHC.
53. 2
nd
Verification that all valves are in their normal operating position.
54. Touch up painting of EcoWater CHC and Filtration components (MECHANICAL) <FSA>
55. Repeat the above for Filtration Systems #2 and #3 if applicable
56. Meet with Customer to discuss findings
57. Review and photograph the following tower elements (MEC)
a.
I would like this to happen on all MECHANICAL visits
b.
Tube bundle condition
c.
Basin condition
i. CHC nozzle function
ii. CHC suction manifold function
iii. Tower pump suction screen (Customer to clean if needed)
d.
Tower spray nozzle function (Customer to clean if needed)
58. Make recommendations to customers (EcoWater CHC Employee)
59. NOTES:
a.
Each section in Ulysses will have a “Notes:” section. Add any pertinent notes to the appropriate section.
b.
Record ANY notes that do not meet the parameters above.
c.
Note ANY customer concerns and or comments.
d.
Copy all customer concerns and comments into EcoWater CHC only notes.
60. EcoWater CHC ONLY NOTES:
a.
Record any notes that you feel need to make EcoWater CHC aware of. These notes are only visible to
EcoWater CHC.
Summary of Contents for CHC Series
Page 1: ...Basics of Service and Troubleshooting ...
Page 36: ...36 ...
Page 37: ...37 ...
Page 77: ...77 Hard Scale from tubes that is hard like Glass ...
Page 82: ...82 6 2 Conductivity Controllers Walchem and LMI ...
Page 83: ...83 ...
Page 84: ...84 ...
Page 101: ...101 6 10 Water Sampling Instructions ...
Page 111: ...111 ...
Page 120: ...120 ...
Page 121: ...121 Eco Water CHC ...
Page 122: ...122 6 15 Electrical Schematics EcoWater CHC ...
Page 123: ...123 CHC EcoWater CHC CHC CHC ...
Page 124: ...124 EcoWater CHC ...
Page 125: ...125 EcoWater CHC ...
Page 126: ...126 EcoWater C HC ...
Page 127: ...127 CHC ...
Page 128: ...128 ...