79
6.1
Corrosion Coupons
All CHC Equipment is supplied with Corrosion Coupon Racks installed. These racks allow for the use
of Corrosion Coupons to measure corrosion rates within the cooling system.
Normally, EcoWater CHC recommends allowing at least 90 days from date of installation before the
initial coupons are installed. These 90 days allow for the system to become accustomed to non-
chemical water treatment, as well as gives the required time to bring the cycles of concentration to their
specified value.
Once the coupons are installed they will be removed and sent to a lab for analysis. The lab will then
issue a report stating the corrosion rates as measured from the before and after coupon weights.
Coupons come in many different metals. They are intended to be placed into our PVC coupon rack for
at least 60 days to yield accurate corrosion rates. CHC’s coupon racks allow for the use of any three
coupons at one time. We recommend selecting a coupon choice that will best represent the metal
content of the cooling system. The coupons that are available from EcoWater CHC include the
following:
Aluminum
Galvanized Mild Steel
Mild Steel
Copper
Stainless Steel
Scale Coupon
EcoWater will supply Maintenance Agreement customers with two sets of coupons per year. The
normal coupon selection depends upon the tower type and its use.
Examples:
If a customer has an Evaporative Condenser with a Galvanized basin, EcoWater CHC will
supply a Scale coupon and a Mild Steel coupon.
If a customer has an Evaporative Condenser with a Stainless Steel basin, EcoWater CHC will
supply a Scale coupon, a Mild Steel coupon and a Stainless Steel coupon.
If a customer has a Cooling Tower with a Galvanized Basin or a Stainless Steel basin,
EcoWater CHC will supply a Scale coupon, a mild Steel coupon and a Copper coupon.
Other coupon configurations are available upon the request of the customer.
Installing the Corrosion Coupons
Most systems includes the provision for conducting Corrosion Coupon Testing. To conduct this test
you will first need to request coupons from EcoWater CHC.
These coupons will be installed for no
less than 60 days before they are removed and weighed. The coupons can be installed up to 120
days before removal.
This installation requires the use of Nitrile Gloves to insure no
contamination of the coupons occur.
Summary of Contents for CHC Series
Page 1: ...Basics of Service and Troubleshooting ...
Page 36: ...36 ...
Page 37: ...37 ...
Page 77: ...77 Hard Scale from tubes that is hard like Glass ...
Page 82: ...82 6 2 Conductivity Controllers Walchem and LMI ...
Page 83: ...83 ...
Page 84: ...84 ...
Page 101: ...101 6 10 Water Sampling Instructions ...
Page 111: ...111 ...
Page 120: ...120 ...
Page 121: ...121 Eco Water CHC ...
Page 122: ...122 6 15 Electrical Schematics EcoWater CHC ...
Page 123: ...123 CHC EcoWater CHC CHC CHC ...
Page 124: ...124 EcoWater CHC ...
Page 125: ...125 EcoWater CHC ...
Page 126: ...126 EcoWater C HC ...
Page 127: ...127 CHC ...
Page 128: ...128 ...