Menu 4-1-6 - Measuring points
The submenu for configuration of the measuring points of the system centre is called using this
button. All important parameters of the S0 and M-bus meters are displayed there. Available M-bus meters are
searched for using the "Refresh" button; see chapter
M-bus Interface for Consumption Data Capture
. The S0
measuring points can be added using the "New entry" button. Already added measuring points can be selected
and configured using the corresponding screen or deleted again.
The screen contains the following parameters:
4-1-6 - Measuring points
Input
Default
Name
Name of the measuring point
max. 19 characters
-
Meter type XX
Selection of the meter type.
After selection of the meter type, this is displayed
graphically,
see legend.
Power
Water
Gas
Heat
Oil
Event
-
Position
Position identifier
max. 5 characters
-
Meter number
Input of the meter number
max. 10 characters
-
Meter constant
Only for pulse meters:
Input of the meter constant (pulses per kWh or m
3
) 1 ..
9999
M-bus meter: Must be set on the meter!
1...9999
-
Transformer constant
Only for pulse meters:
Input of conversion ratio of the current transformer
1..255
M-bus meter: Must be set on the meter!
1..255
-
Meter reading index
Only for M-bus meters:
If the "Determine index automatically" option is activated
(factory setting), the meter value (electricity (kW), water
(m³), etc.) to be archived is determined automatically.
If an alternative meter value should be archived, the
meter reading index must be configured for this. The
meter reading index can be determined using the
"Retrieve meter data" button. The meter indexes in the
meter data can be found via the designation
"DataRecord id=xxx)" whereby "xxx" stands for the
index.
Example
:
Retrieval of the meter data
Retrieval of the meter data can be initiated to test the
communication with the M-bus meter. This data retrieval
is initiated by tapping the button
Practical tip
: in the event of communication faults on
the M-bus, this can also be used to check whether the
communication is still functioning.