Firmware V7.16.x
16.05.2023
88/183
•
•
•
•
7.2.3
SIOX – Terminal assignment of the 230 V AC digital inputs
There are 12 floating digital inputs (230 V AC) available per SIOX extension module for system monitoring and/
or as measuring points ( meter inputs).
Note
: The digital inputs of the SIOX extension module in the example are used as follows:
All signals have the same outer conductor (L).
A2..H2 are connected to N.
The first two digital inputs 1(A1/A2) and 2 (B1/B2) are used for system monitoring.
A signal of 24 V AC/DC is detected at the last digital input 12 via a coupling relay.
•
•
•
•
DANGER
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock!
BEFORE
connecting and disconnecting, it
must
be checked that surrounding connections are in a
de-energised
state!
Overvoltage category II / contamination degree 2:
All connections of the device provided for
operation with 230 V AC supply voltage
must
be wired with the same outer conductor (L). 400 V
AC between neighbouring connection terminals is
not
permitted!
All digital inputs on the expansion modules are factory-set to 230 V AC.
Wiring of the digital inputs:
The N conductor
must
be applied at a terminal level (A2..L2 / 50..72)!
Practical tip:
Signals of 24 V AC/DC
must
be detected via coupling relays. For pulse counters with
pulse measuring or transistor interface the use of SSR coupling relays is required, for further details
see chapter
SIOX - connection of energy, gas, water and event meters
.
ATTENTION
Detailed safety instructions and information for the configuration of the jumpers for the digital inputs are
provided in chapter
SIOX - Konfiguration der Jumper
.