GLT Type Mix 3000
There are both GLT components of the 5000
family as well as GLT components of the 3000
family on the CAN bus. The operation of both
families is not supported by the system centre
in the Virtus 5 family.
Remove the GLT components of the
3000 family or remove the GLT
components of the Virtus 5 family
0
GLT Type Mix 5000
There are both GLT components of the 5000
family as well as GLT components of the 3000
family on the CAN bus. The operation of both
families is not supported by the system centre
in the Virtus 5 family.
Remove the GLT components of the
3000 family or remove the GLT
components of the Virtus 5 family
0
GLT configuration missing
The GLT configuration of the GLT components
in the Virtus 5 family could not be transmitted
to the system centre.
Check:
Wiring of the CAN bus
CAN bus length (max. 500 m)
No branch lines
CAN-GND must be available
everywhere
CAN bus termination 100 ohms
Colour scheme complied with
Correct cable type (LiYCY 2 x 2
x 0.75 mm² with 120 ohms
characteristic impedance)
Configuration of the GLT
components of the Virtus 5
family
47
Time adjustment
The time in the system centre has been
adjusted.
---
48
Date adjustment
The date in the system centre has been
adjusted.
---
Verst. System time
The date and time in the system centre have
been adjusted.
---
Verst. Time zone
The time zone of the system centre has been
adjusted.
---
51
Restart: POR
Restart: WDG
Restart: RST
The controller has been restarted for the
following reasons:
POR = power failure
WDG = hardware watchdog
RST = manual reset or reset by
watchdog
---
88
M-bus response missing
At least one M-bus meter is not providing any
data
Check:
Cabling of the M-bus
Configuration of the M-bus
gateway
89
M-bus failure
Failure of the M-bus
98
Load shedding
Load shedding active
---
VerstKonfig Tageb.
Change of the log
---
153
Delete 24h list
Archiving: Temperature data deleted
Delete operating data
Archiving: Operating data archives deleted
---
Delete energy data
Archiving: Energy data deleted
---
241
VerstKonfig Al.Ein.
Configuration change: Signal inputs
---
VerstKonfig Alm-Cfg
Configuration change: Alarm settings
---
VerstKonfig Lastab.
Configuration change: Load shedding
---
VerstKonfig M-Zlr
Configuration change: M-bus meter
---