Firmware V3.00
05.08.2019
27/100
CI 4x00:
All 10 temperature sensors are supported in system centres.
CI 3x00:
Whether the version in use supports this function can be checked in the System Centre / Store
Computer User Guide. Store Computers of all versions are always capable of archiving two temperatures.
The data of the case controller and of the temperature recording controller UA 410 L are archived in the system
centre / store computer. Operating status of the case/coldroom controller (defrost, cooling, manual shutdown,
etc.) is combined with the temperature data recorded by the temperature-recording controller.
Parameters
The to parameters EU Archive CAN und EU Archive Zone on the Temperature Data Logging Controller are
used to allocate each sensor to case/coldroom controller. If the parameter EU-Archiv CAN is set to “--”, no
archiving of the temperature values recorded by the temperature recording controller is performed in the
system centre / store computer.
With all, the recording interval is 15 minutes and data is archived for a period of one year.
Temperature sensors of type L243 must be connected to the UA 410 L for temperature recording in
compliance with EU Regulation DIN EN 12830! Actual temperature control must always be performed
by an
independent
case/coldroom controller, e.g. UA 400.
Conditions to be fulfilled:
1. The UA 410 L
must
be integrated together with a system centre / store computer in the E*LDS CAN
bus system.
2. UA 410 L must not be used simultaneously for controlling the same refrigeration points.
3. UA 410 L
must
have temperature sensors of its own.
DIN EN 12830 requires regular testing in accordance with DIN EN 13486 for temperature measuring
recorders when they are in operation. See Section
for details of usability of
the UA 410 L in accordance with DIN EN 12830.
Recording of controller temperatures no longer complies with the EU Regulation when the EU Archive
CAN parameter is set to”-”!