Firmware V3.00
05.08.2019
65/100
7.8 Terminal assignment of the 24 V DC transistor outputs
Controller Type Digital output 1
81: 24 V DC / max. 50 mA
82: OUT
83: GND
Digital output 2
91: 24 V DC / max. 50 mA
92: OUT
93: SHIELD
UA 410 L
Without function
Without function
Warning - hazardous electrical voltage!
Connecting mains power to the transistor outputs will lead to
the destruction of the controller!
Destruction of the transistor outputs!
Due to the capacity of the transistor outputs ofa max. of 50
mA, 24 V DC coupling relays must be used for controlling the load.
If any transistor output is activated by the controller, the associated green LED lights,
see
chapter
for details. For further details on the function of the transistor outputs
see
chapter
Wirksinn der Relais- und Transistor-Ausgänge
.