Firmware V3.00
05.08.2019
42/100
6.4 Basic configuration of the controller
The lock-down must previously be deactivated on the higher level controller (system centre / store computer or
operator terminal) so that configuration settings can be made on the controller.
1. Deactivating the input lock-down
1.
BT 300 operator interface See
chapter
Lock-down of the setpoint change
for details.
2.
System centre Via Login symbol; see
chapter
for details.
3.
Store computer / operator terminal Menu 9-3; see
chapter
Store computer CI 3x00 / operator terminal AL
for details.
2. Opening main menu of the controller
1. The main menu of the controller is shown directly in the operator interface.
2.
In the system centre, select the required controller in
Menu 4-2
and then tap the
Remote Control
button to
display the main menu of the controller. See
chapter
for details.
.
3. In the store computer and operating terminal, a selection list of all CAN bus components is displayed in
Menu 5 Remote Control. Select the controller with the corresponding CAN bus address (Kn,nnn = 1..99) in
the selection list to be parametrised using the cursor or direct input and recall by tapping the
ENTER
button
so that the main menu of the controller is displayed. See
chapter
Store computer CI 3x00 / operator terminal
2a. Special case UA 410 L
In contrast to the other controllers in the UA 400 series, the required sensor must be selected previously on the
UA 410 L to reach the main menu of any temperature sensor (Rx.1 ... Rx0):
Main Menu
REFR. PT. POS: XXX
1 Temp. Rx.1
Selection field 1st temperature sensor Rx.1 - Text freely selectable, see Menu 6-1
2 Temp. Rx.2
Selection field 2nd temperature sensor Rx.2 - Rx.2 - Text freely selectable, see Menu 6-1
...
...
0 Temp. Rx.0
Selection field 10th temperature sensor Rx.0 - Text freely selectable, see Menu 6-1