Firmware V3.00
05.08.2019
18/100
5 Function of UA 410 L
5.1 Starting characteristics
The following are distinguished for any start-up of the controller:
•
First start
•
Restart
5.1.1 First start- reset controller to factory settings
The first start can be initiated using the following procedure:
1. Disconnect controller from the power supply for safety reasons (make a note of the DIP switch S3 settings
(e.g. OFF-ON-OFF-...).
2. Adjust settings at the DIP switch S3 (e.g. OFF-OFF-OFF-...).
3. Power on the controller again and wait approx. 1 minute while the controller starts up.
4. Disconnect controller from the power supply for safety reasons.
5. Reset DIP switch S3 to the noted starting position.
6. Switch on controller again.
7. The settings of the controller have been reset to the factory settings.
5.1.2 Restart - restart of the controller
For a restart, the device is restarted with all configured parameters and the CAN bus address set on the rotary
switch. A restart can be initiated using the following procedure:
•
disconnection and reconnection of the power supply
Parameters mentioned in this section are described in the
section. It will normally not be
necessary to change the default settings of these parameters. Parameters that do not allow changing
are termed fixed parameters below.
Caution: data loss!
A first start causes all parameters to be reset to the factory settings!
A first start is also performed when a different controller version (e.g. UA 400 UA 410 D UA 400 E UA
410 L) is loaded on the controller via firmware update. A sensor scan (Menu 6-1)
must
be performed
during commissioning or after a first start! The sensor scan is the only possibility to define the sensors
to be monitored; see chapter
.