Firmware V3.00
05.08.2019
96/100
12 Specifications of UA 410 L
12.1 Electrical data
UA 410 L AC
Power supply
230 V AC (/- 10%), 50/60 Hz (/- 3 Hz)
Rated power
11 VA
Leakage current over PE
Max. 1 mA
Rated
surge
voltage
2,5 kV (Overvoltage category II)4,0 kV (Overvoltage category III)
Relay outputs
Relay
:
4 (N.O.) x 230 V AC, floating, min 10 mA load type: ohmic max. 6 A inductively
max. 3 A, cos = 0,4
3 (O.C.) x 230 V AC, floating, min 10 mA load type: ohmic max. 6 A inductively
max. 3 A, cos = 0,4
Transistor outputs
2 x 24 V DC pulldown, Switching transistor with internal current limiting to 50 mA
Digital inputs
4 x 230 V AC floating
Analogue inputs
10 temperature sensors, two-wire typefor sensor types L243 / K243, K277,
5K3A1 (No shielding is required on sensor leads when installed exclusively
inside the refrigerated display case and when external interference (for example
from parallel power wires) is not to be expected)
2 x 4..20 mA *
Analogue
outputs
*
2 x 0..10 V short-circuit proof
Realtime clock
Battery-backed, Lithium cell (shelf life 10 years), type CR 2450N, 3V lithium
Accuracy: typically 12 min/yr at 25 °C
Fieldbus port
CAN bus, floating
Data port
DISPLAY: BT 300x Operator terminal and up to 4 BT 30 Temperature displays
CI320 (TTY) Communication with the PC software for reading off the operating
data
USB interface
For firmware update (in future it will be possible to connect a notebook (PC) to
this interface for the direct parameterisation via LDSWin)
Monitoring function
Watchdog
Environmental conditions
Temperature range
Transport: -20 °C ... +80 °C / Operation: 0 °C ... +50 °C
Temperature change
Transport: max. 20 K/h / Operation: max. 10 K/h
Relative humidity(non-condensing)
Transport: 8 % ... 80 % / Operation: 20 % ... 80 %
Warning - hazardous electrical voltage!
Danger of electric shock!
Overvoltage category III (test voltage 4,0 kV)
/ pollution degree 2:
All device connections designed for use with 230 V AC supply voltage
must
be connected to the same
phase conductor.
400 V AC between neighbouring connection terminals is
not
permitted!
Overvoltage category II (test voltage 2,5 kV)
/ pollution degree 2
or
Overvoltage category II (test
voltage 2,5 kV) / pollution degree 1:
Different phase conductors may be used. 400 V AC between neighbouring connection terminals is
permitted!