LPT-11 Transient Immunity
Item Check
When
Completed
Description
21
If 1.0kV or 2.0kV surge immunity is desired, an appropriate
TVS device from table 6.1 is placed differentially across
NET_A and NET_B. For 0.5kV surge immunity, no TVS
should be needed.
22
The device's package is designed to prevent ESD hits from
arcing into the node's internal circuitry.
LPT-11 Transceiver Programming
Item Check
When
Completed
Description
23
The standard TP/FT-10 channel is defined for the device (for
devices with Neuron chip clock rates of
≥
5MHz only).
24
If the device operates with 2.5MHz Neuron Chip clock, it will
not be used on any networks that use the standard TP/FT-10
comm parameters.
Link Power Network Considerations
Item Check
When
Completed
Description
25
The network uses a wire type listed in tables 5.2 and 5.3.
26
The network length obeys the datacomm transmission
specifications described in tables 5.2 and 5.3.
27
The network also obeys the power-limited distance
specifications described in chapter 5 (either the Simplified
Form or the Extended Performance Form).
28
If the network configuration is Free Topology, one LPI-10
Source Coupler is used anywhere in the network to provide
power to the network, and the LPI-10 Source Coupler’s
termination jumper is in the “1CPLR” setting.
C-4 Appendix C - Checklist