L
ON
W
ORKS
LPT-11 Transceiver User’s Guide
5-7
Table 5.4
Simplified Power Specifications Using Belden 85102 or Belden
8471 (16AWG/1.3mm) Wire
Nominal
Worst
Case
Units
500 meter branch length,
Evenly distributed loading along a bus
application current:
25 mA
128
128
devices
50
mA
64 64
100
mA
32 32
500 meter branch length,
Lumped loading or otherwise distributed
application current:
25 mA
112
81
devices
50
mA
56 40
100
mA
28 20
400 meter branch length,
Lumped loading or otherwise distributed
application current:
25 mA
128
101
devices
50
mA
64 50
100
mA
32 25
Table 5.5
Simplified Power Specifications Using JY (St) Y 2x2x0.8 Wire
Nominal
Worst
Case
Units
320 meter branch length,
Evenly distributed loading along a bus
application current:
25 mA
128
96
devices
50
mA
64 48
100
mA
32 24
320 meter branch length,
Lumped loading or otherwise distributed
application current:
25 mA
64
48
devices
50
mA
32 24
100
mA
16 12
160 meter branch length,
Lumped loading or otherwise distributed
application current:
25 mA
128
96
devices
50
mA
64 48
100
mA
32 24