LPT-11 Transceiver User’s Guide
5-5
System Specifications
• Up to 128 LPT-11 transceivers or 64 FTT-10A/FT 31xx transceivers are allowed per network
segment.
• 1 Link Power Unit Load (LPUL) = 25ma@Vcc=5V. Therefore, 4 LPULs = 100ma, the
recommended maximum for a single LPT-11 transceiver.
• Both types of transceivers may be used on a given segment, provided that the following
constraint is met:
(1 x number of LPT-11 transceivers) + (2 x number of FTT-10A transceivers)
≤
128
• The average temperature of the wire must not 55°C, although individual segments of
wire may be as hot as +85°C.
• The sum of the application current of all the devices in a segment must not exceed 3.2A at
+5V.
Transmission Specifications
Table 5.2
Doubly-Terminated Bus Topology Specifications
Maximum bus length
Maximum stub length
Units
Belden 85102
2200
3
meters
Belden 8471
2200
3
Level 4/22AWG
1150
3
JY (St) Y 2x2x0.8
750
3
Category 5
725
3