The following figure depicts twisted pair networks running in outdoor locations.
Figure 6.3
Network and Shield Lightning Protection
For maximum surge protection,
every
LPT-11 link power device on the network
segment, whether located indoors or outdoors, has the protection circuitry described
in the previous section. This is in addition to any building entrance protection
devices present on the network.
EN 61000-4 Electromagnetic Compatibility (EMC) Testing
Echelon has tested the LPT-11 transceiver operating in typical two-layer application
boards to verify that the transceiver complies with the five applicable EN 61000-4
test requirements (formerly known as IEC 1000-4 tests). Provided that a device’s
PCB is designed following the guidelines in Chapter 2, the LPT-11 transceiver
should pass the EN 61000-4 tests described in table 6.2.
Table 6.2
EN 61000-4 Test Immunity Levels
EN Test
Description
LPT-11
Immunity Level
EN 61000-4-2
ESD
Level 4
EN 61000-4-3
Radiated Susceptibility
Level 2
EN 61000-4-4
Burst
Level 4
EN 61000-4-5
Surge
Level 3*
EN 61000-4-6
Conducted RF Immunity
Level 3
* Level 3 may be obtained with addition of TVS between NET_A and NET_B.
6-8
Design
Issues