EPX400-A20CU – Manual
Page 41 / 62
Serial port settings
8.5.1.
The selected parameters shall correspond to RS-232 port settings in device which will
be connected to the communicator. Available parameters are shown in the table
below:
Parameter
Value
Baud rate (bits/sec)
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Data bits
8
Parity
None, Even, Odd
Stop bits
1, 2
Flow control
None, RTS, CTS, RTS/CTS
If RS232 checkbox will not be enabled, data to the Event monitor will be sent on
device’s serial port. With this setting, GD-PROG cable can be used to observe device
state using EBS Config 2.0
Buffer flushing
8.5.2.
Data received from connected device are stored in communicator buffer. Buffer
capacity is 511 bytes. Define criteria that meeting shall mean data transmission to
monitoring system communicator. The following options are available:
- After receiving defined ASCII character
- After expiry of defined time
- After receiving defined amount of characters
For every option list of available values are provided, and they me be scrolled down
after clicking on adequate arrow.
The communicator controls buffer contents in respect of meeting of determined
criteria. It is performed with the following order: selected character, time, number of
characters.
Discharge of buffer (transmission) follows if one criteria is fulfilled.