Connecting the power supply
15
07/09 MN03407002Z-EN
Figure 9: Connecting the power supply
The terminals are suitable for AWG22 to AWG16 cables and
for flexible cables with a cross-section of 0.5 to 1.5 mm².
Tighten the terminals to 06 Nm.
24V
0.6
x
3
.5
L01+
L01–
1 A
3
A
U
e
= 24 V
H
(20.4 – 28.8 V
H
)
0V24V 0V
0.6 Nm
h
The gateway is protected by a 1 A gG/gL line protection
fuse or a 1 A miniature circuit-breaker featuring
characteristic C. The fusing of the incoming supply for the
contactor coils is implemented using 3 A gG/gL fuses or a
3 A miniature circuit-breake featuring characteristic Z.
j
Danger!
In safety-relevant applications the power supply providing
power to the SmartWire system must feature a PELV
power supply unit (protective extra low voltage).