Data mapping of SmartWire
stations
37
07/09 MN03407002Z-EN
Table 19: SWIRE-4DI-2DO-R status data, register area 40014 –
40017
Regis
ter
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
40014 Low
byte
-
-
-
-
-
-
-
-
High
byte
SWIRE-
4DI-2DO-R
status
-
-
-
Input I4
Input I3
Input I2
Input I1
40015
Low
byte
-
-
-
-
-
-
-
-
High
byte
-
-
-
-
-
-
-
-
40016
Low
byte
-
-
-
-
-
-
-
-
High
byte
-
-
-
-
-
-
-
-
40017
Low
byte
-
-
-
-
-
-
-
-
High
byte
-
-
-
-
-
-
-
-
h
Whether it is best to select an abbreviated or a full data
representation depends on the type of SmartWire station:
An abbreviated representation is best suited for stations
with a small number of status or control bits, as this
reduces the number of unused bit fields within the
MODBUS RTU protocol; a full representation is best used
for stations with a large number of status or control bits.