background image

 

12

Sonix 2Mx Technical Manual

SONIX 2MX TECHNICAL MANUAL  

TM370 / A  June 2022  www.eaton.com

6.1.6  Alarm activity

There are 6 alarm activity indicators numbered 1 to 6, 

each one will reflect the corresponding alarm being 

active on the system. Internal to Sonix there are 6 

additional alarms, 7 to 12, that are reflected on the 

indicators by flashing the corresponding number. The 

flashing is overridden by the higher priority alarm being 

active

Alarm 

indicator

Off

Slow 

flashing

Solid

1

Alarms 1 or 7 

are not active

Alarm 7 is 

active

Alarm 1 is active 

(Alarm 7 may or may not be 

active)

2

Alarms 2 or 8 

are not active

Alarm 8 is 

active

Alarm 2 is active 

(Alarm 8 may or may not be 

active)

3

Alarms 3 or 9 

are not active

Alarm 9 is 

active

Alarm 3 is active 

(Alarm 9 may or may not be 

active)

4

Alarms 4 or 10 

are not active

Alarm 10 

is active

Alarm 4 is active 

(Alarm 10 may or may not be 

active)

5

Alarms 5 or 11 

are not active

Alarm 11 

is active

Alarm 5 is active 

(Alarm 11 may or may not be 

active)

6

Alarms 6 or 12 

are not active

Alarm 12 

is active

Alarm 6 is active 

(Alarm 12 may or may not be 

active)

Table 12 - Alarm indicator states

6.1.7  Beacon activity

The beacon activity indicator has only two states:

Pattern

State

Off

No beacon activity

Solid

A beacon output is active on the system

Table 13 - Beacon activity indicator states

6.1.8  Local Status indicators

The local status indicators are comprised of a pair of Red 

and Green LEDs per Sonix bus type.

The bus types covered are as follows:

• 

Matrix: 

shows status relating to the 2Mx’s  

 

internal monitoring

• 

HMI: 

shows status relating to all access  

 

panels and Hmi-Tu’s

• 

Amplifier: 

shows status relating to all amplifiers

• 

Beacon : 

shows status relating to all beacon   

 controllers

• 

I/O: 

shows status relating to all IO Bus  

 

items: Io, MS12, and PBx

• 

Power Dist:   shows status relating to all power   

 

unit modules

Each LED pair has a set of fixed possible states:

Pattern

State

Both off

Error – not a valid state

Solid Green

Healthy, no issues

Fast Flashing  

Green

Duplicate unit ID seen, not affecting system operation 

but should be corrected as soon as practicable

Solid Green + Slow 

Flashing Red

Healthy but ‘latched’ a previous/temporary fault

Fast Flashing Red

Split loop detected

Solid Red

Fault

Table 14 - Local system status indicator states 

For a detailed explanation of the faults and causes please 

refer to section 10 and the Sonix Software manual.

6.1.9  Default Config

This indicator is not currently used, reserved for  

future expansion.

6.1.10  Global Status

The global status indicators are made up of 3 pairs of 

LEDs, one Red and  one Green for each of the three 

groups:

• 

System Sync - Indicates status of the system-system 

synchronisation bus

• 

N+1 Switchover - Indicates status of 2Mx when 

configured in N+1 mode

• 

Global Bus - Indicates status of the global bus

The System sync indicators are enabled when the 2Mx 

is configured to be part of a connected system e.g. N+1 

or AB.

Pattern

State

Off

Global Sync  Bus monitoring disabled (both audio and data)

Solid Green

Healthy, no issues

Solid Green + 

Slow Flashing Red Healthy but ‘latched’ previous/temporary fault
Fast Flashing Red

Split loop detected

Table 15 - System Sync indicator states

The N+1 indicators show the state of N+1 redundancy 

fail-over and will depend on whether the 2Mx is 

configured as the primary or secondary controller:

Pattern

Primary controller 

state

Secondary controller 

state

Off

N+1 mode disabled

Solid Green

Primary controller healthy 

in control

Solid Green + 

Solid Red

Primary controller faulty 

and secondary controller 

is not detected

Slow Flashing 

Green

Secondary controller healthy 

in standby

Solid Green + 

Slow Flashing 

Red

Secondary controller healthy 

and primary controller is not 

detected

Solid Red

Primary controller faulty 

BUT secondary controller 

is detected

Secondary controller faulty 

BUT primary controller is 

detected

Table 16 -  N+1 indicator states 

ote: 

N

The N+1 indicators are only active when the 2Mx controller has 

been configured in N+1 mode.

Summary of Contents for SONIX 2Mx

Page 1: ...Alarms Important Message AUX OPERATIONAL Beacons System Reset Beacon Test Global Ticktone Global Sense Test LOCAL STATUS Matrix HMI Amplifier Beacon I O Power Dist Default Config Bgm 1 2 3 4 5 6 1 2 P...

Page 2: ...FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF T...

Page 3: ...feedback 2Mx Sonix 2Mx Central controller Amp 350 d Sonix 350 W Power Amplifier with 100 V line output Eol1 Sonix Remote End of Line unit Eol8 Sonix Amplifier to 100 V line interface unit 8 channel SP...

Page 4: ...Port Indicators 9 5 4 2 Bus connections 10 5 4 2 1 Split loop 10 5 4 3 Audio 10 5 4 4 Global bus 10 6 UNIT OPERATION 11 6 1 Front panel interface 11 6 1 1 Power on reset 11 6 1 2 Power 11 6 1 3 Backgr...

Page 5: ...g 22 8 7 1 Data monitoring 22 8 7 2 Missing unit monitoring 22 8 7 3 Audio monitoring 22 8 7 4 Unit monitoring 22 8 8 Global Sense test 22 8 9 Access panel timeout 22 8 10 IO Audio timeout 22 9 CUSTOM...

Page 6: ...N 1 TAP PCB CAT6A CONNECTIONS 19 FIGURE 18 N 1 TAP PCB CONTROL CONNECTIONS 20 FIGURE 19 2MX FAULT TREE 24 LIST OF TABLES TABLE 1 FAULT OUTPUT STATES 9 TABLE 2 DEFAULT CONFIGURATION INPUT STATE 9 TABLE...

Page 7: ...nfigurable to allow customisation and modification to the whole Sonix PA GA system Central to the architecture of the Sonix PA GA system is a fully redundant self healing data loop connected via RJ45...

Page 8: ...5 Beacon Bus Beacon bus connections 6 Sync Bus Sync bus connections 7 Power Bus Power bus connections 8 48V Input DC Input connector 9 Fault Output Fault relay output 10 Default Config Communications...

Page 9: ...T6A The 8off pairs of both 8p8c RJ45 style sockets on the rear of the 2Mx are used to connect and communicate with the other units of a Sonix PA GA system Name Color Connected units Data Audio Amp Gre...

Page 10: ...5 Split loop bus data flow The only exception to this is the global bus which is not capable of being a loop 5 4 3 Audio Audio is routed in a similar arrangement to the data control flow There are 2...

Page 11: ...Sonix Hmi 26 see section 8 1 for more details 6 1 4 Local source inputs The local source inputs are comprised of Aux I P and PABX groups Each group has two indicators labelled 1 and 2 The indicators a...

Page 12: ...ible states Pattern State Both off Error not a valid state Solid Green Healthy no issues Fast Flashing Green Duplicate unit ID seen not affecting system operation but should be corrected as soon as pr...

Page 13: ...s not available for normal operation without accepting the ping set request first 6 1 13 Internal Fault Buzzer The 2Mx is provided with an internal buzzer that activates each time a new fault occurs T...

Page 14: ...mplifiers Vw2 Beacon Controller Vw2 Beacon Controller Pbx Fire Gas Ms12 Io Io PABX 2Mx Central Controller 2Mx Central Controller 350 d Ampli er 350 d Ampli er 350 d Ampli er 350 d Ampli er 350 d Ampli...

Page 15: ...Ampli er 350 d Ampli er 350 d Ampli er 350 d Ampli er 350 d Ampli er Vw2 Beacon Controller Vw2 Beacon Controller Controller Vw2 Beacon Controller 2Mx Central Controller 2Mx Central Controller 350 d A...

Page 16: ...Controller Vw2 Beacon Controller Ms12 A Side Access Panel Access Panel Access Panel Access Panel Access Panel Fire Gas Ms12 Pbx Vw2 Beacon Vw2 Beacon Vw2 Beacon Vw2 Beacon Controller Controller Contr...

Page 17: ...er 350 d Ampli er 350 d Ampli er 350 d Ampli er 350 d Ampli er 350 d Ampli er 350 d Ampli er 350 d Ampli er 350 d Ampli er 350 d Ampli er Vw2 Beacon Controller Vw2 Beacon Controller Controller Vw2 Be...

Page 18: ...ler Controller Vw2 Beacon Controller Pbx Access Panel Access Panel Access Panel Access Panel Access Panel Fire Gas Pbx Ms12 Vw2 Beacon Vw2 Beacon Vw2 Beacon Vw2 Beacon Controller Controller Controller...

Page 19: ...ap PCB is required for Amplifier Bus and a second for Beacon Bus if in use The connections for the beacon bus follow an identical pattern to amplifier bus connections shown Unit N Unit 1 Unit 2 Amp Bu...

Page 20: ...ts of the resolved priority and general operation fault diagnostics The recommended maximum cable run for the sync bus is 100m please discuss with your local Eaton representative on longer distances 7...

Page 21: ...Software See SAS manual for details 8 2 3 Amplifier faults In a typical PA GA system amplifiers are the most numerous items To aid with issue tracking the extended 2Mx Sync status report into SAS incl...

Page 22: ...o returning A warning will be raised if a bus stops being a complete loop for audio see 6 1 8 Local Status indicators ote N Hmi Bus connected units access panels are partly wired in spurs they also mo...

Page 23: ...Alarm Tone that is mixed into the Emergency Speech broadcast is set to approximately 12dB lower than the normal Attenuated Alarm This value can be customised to one of the following 1 1 2 5 4 6 8 5 1...

Page 24: ...se Fault Split Loop Solid RED Key Flashing RED Flashing GREEN Ms12 Fault Io Audio Input Fault Amplifier Fault Missing Unit Missing Unit Duplicate Unit ID Duplicate Unit ID Duplicate Unit ID Data Routi...

Page 25: ...red indicator is informing the user that there was an issue on the associated bus but it has been resolved To diagnose the issue users will need to study the log included with SAS assuming that the s...

Page 26: ...aton and SONIX are registered trademarks All other trademarks are property of their respective owners Changes to the products to the information contained in this document and to prices are reserved s...

Reviews: