4 Commissioning
4.4 Acyclic data
DX-NET-SWD
06/13 MN04012009Z-EN
www.eaton.com
47
4.4.3.4 Fault numbers
Faultnumber
[hex]
Value shown on display
Description
00
StoP
Stop, ready for operation
7112
OI-b
Brake chopper overcurrent
7114
OL-br
Braking resistance overload
2220
O-I
• Overcurrent at variable frequency drive output
• Motor overload
• Overtemperature on variable frequency drive heat sink
7131
I_t-trP
Motor, thermal overload
5400
PS-trP
Internal fault (power section)
3210
O_Vo I&
Overvoltage (DC link)
3220
V_Vo I&
Undervoltage (DC link)
4230
O-&
Overtemperature (heat sink)
4220
V-&
Undertemperature (heat sink)
6300
P-dEF
Default settings (parameters have been loaded)
9000
E-triP
external error message
7510
SC-trP
Field bus error
5130
reserved
3130
P-LOSS
Phase failure (mains side)
2213
SPIn-F
Motor pick-up control function (for catching spinning motors)
failed
4231
th-Flt
Internal thermistor fault (heat sink)
7601
dAtA-F
EEPROM checksum fault
7350
4-20 F
Analog input:
• Out-of-range value
• Wire breakage (4-mA monitoring)
Summary of Contents for PowerXL DX-NET-SWD
Page 4: ...II ...
Page 10: ...0 About this Manual 0 6 Units 6 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 16: ...1 Device series 1 7 Disposal 12 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 26: ...3 Installation 3 4 Dismantling 22 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 64: ...4 Commissioning 4 5 SmartWire DT diagnostics 60 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 68: ...5 Appendix 5 2 SmartWire DT 64 DX NET SWD 06 13 MN04012009Z EN www eaton com ...