![Eaton PowerXL DX-NET-SWD Manual Download Page 27](http://html1.mh-extra.com/html/eaton/powerxl-dx-net-swd/powerxl-dx-net-swd_manual_4028938027.webp)
4 Commissioning
4.1 DX-NET-SWD3 with DC1 variable frequency drive
DX-NET-SWD
06/13 MN04012009Z-EN
www.eaton.com
23
4 Commissioning
4.1 DX-NET-SWD3 with DC1 variable frequency drive
For SmartWire-DT operation, the parameter P-12 must be set on variable
frequency drive DC1; versions 9 - 13 are available for this purpose.
Other parameters do not have to be set.
→
Complete all measures for commissioning the DC1 variable fre-
quency drive as described in the manual MN04020003Z-EN.
→
Check the settings and installations for the connection to the
SmartWire-DT system which are described in this manual.
NOTICE
Make sure that there is no danger in starting the motor.
Disconnect the driven machine if there is a danger in an incorrect
operating state.
→
The following parameter settings listed below are required for
operation with SmartWire-DT.
Valule P-12
Description
0
Control signal terminals
1
HMI device (Keypad FWD)
2
HMI device (Keypad FWD/REV)
3
Modbus with internal ramp time
4
Modbus with ramp time via bus
5
PI controller with external actual value
6
PI controller with external actual value and totalized value of AI1
7
CANopen with internal ramp time
8
CANopen with ramp time via bus
9
SmartWire-DT operation with setpoint value via SmartWire-DT
10
SmartWire-DT operation with local setpoint value
11
Local operation with setpoint value via SmartWire-DT
12
Actuation via SmartWire-DT - depending on the settings with the loss in
communication, automatic change to the local actuation
13
Operation and setpoint value via SmartWire-DT with enable via terminal
→
Further information about parameter P-12
Summary of Contents for PowerXL DX-NET-SWD
Page 4: ...II ...
Page 10: ...0 About this Manual 0 6 Units 6 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 16: ...1 Device series 1 7 Disposal 12 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 26: ...3 Installation 3 4 Dismantling 22 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 64: ...4 Commissioning 4 5 SmartWire DT diagnostics 60 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 68: ...5 Appendix 5 2 SmartWire DT 64 DX NET SWD 06 13 MN04012009Z EN www eaton com ...