4 Commissioning
4.4 Acyclic data
40
DX-NET-SWD
06/13 MN04012009Z-EN
www.eaton.com
620
1
rw
U16
Drive stop mode
P-05
0 - 2
0: Stop with ramp
1: free run-down
2: Stop with ramp 2
620
0
rw
U16
Drive start function - Terminal
mode
P-30
0 - 6
0: deactivated. (The variable
frequency drive will need a new
start edge): After being
switched on, as well as after a
reset, the variable frequency
drive will not start if digital
input 1 remains closed. The
input must be closed
after
switching on, or after the reset,
in order to start the variable
frequency drive again.
1: Auto_0 ; starts automatically
(the converter does not need a
start edge, signal is active
again)
2 : Auto_1 ; Will start automat-
ically once
3 : Auto_2 ; Will start automat-
ically twice
4 : Auto_3 ; Will start automat-
ically 3 times
5: Auto_4 ; Will start automati-
cally four times
6: Auto_5 ; Will start automati-
cally five times
620
3
rw
U16
Drive start function - Scanning
mode
P-31
0 - 3
REAF, start function with auto-
matic restart, operating unit.
This parameter will only be
active if the keypad control
operating mode is being used
(P-12 = 1 or 2).
0: Minimum speed; keypad
1: Previous speed; keypad
2: Minimum speed; terminal
3: Previous speed; terminal
626
1
rw
U16
Optimum energy consumption
P-06
0 - 1
0: deactivated
1: activated
626
0
rw
U16
Parameter access lock
P-38
0 - 1
0 : deactivated
1: activated
635
0
rw
U16
Rotary start enable / DC injection
at enable
P-33
0 - 1
0: deactivated
1: activated
682
0
rw
UInt16
Motor overload protection
P-51
0 - 1
0: thermal image is lost when
switching off
1: thermal image remains when
switching off
PN
U index
PN
U subindex
Access
right
Data
type
Meaning
Display
number
Value Range
Description
Summary of Contents for PowerXL DX-NET-SWD
Page 4: ...II ...
Page 10: ...0 About this Manual 0 6 Units 6 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 16: ...1 Device series 1 7 Disposal 12 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 26: ...3 Installation 3 4 Dismantling 22 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 64: ...4 Commissioning 4 5 SmartWire DT diagnostics 60 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 68: ...5 Appendix 5 2 SmartWire DT 64 DX NET SWD 06 13 MN04012009Z EN www eaton com ...