4 Commissioning
4.4 Acyclic data
46
DX-NET-SWD
06/13 MN04012009Z-EN
www.eaton.com
4.4.3.3 Parameter P15 (PNU 423)
SWD mode (P12 = 9 - 13)
P-15
DI1
DI2
DI3/AI2
AI1/DI4
Notes
0
0 = Blocked
1 = Start enable
0 = FWD
1 = REV
0 = Selected setpoint source
1 = Fixed frequency 1 (P-20)
Setpoint value
AI1
1
0 = Blocked
1 = Start enable FWD
0 = Selected setpoint
source
1 = Fixed frequency 1/2
0 = Fixed frequency 1 (P-20)
1 = Fixed frequency 2 (P-21)
Setpoint value
AI1
2
0 = Blocked
1 = Start enable FWD
DI2
DI3/AI2
DI3/AI2
Fixed
frequency
0 = Fixed
frequency 1 - 4
(P-20 - P-23)
1 = maximum
frequency (P-01)
4 selectable fixed frequen-
cies:
The analog input is used as
digital input.
Switched at:
8 V < V
input
< 30 V
0
0
0
FF1 (P-20)
1
0
0
FF2 (P-21)
0
1
1
FF3 (P-22)
1
1
1
FF4 (P-23)
3
0 = Blocked
1 = Start enable FWD
0 = Selected setpoint
source
1 = Fixed frequency 1 (P-20)
External fault:
0 = Fault
1 = Run
Setpoint value
AI1
Connection of an external
thermistor of type PT100 or
similar to DI3
4
0 = Blocked
1 = Start enable FWD
0 = Analog input 1
1 = Analog input 2
Setpoint value AI2
Setpoint value
AI1
Changing between analog
input: 1 and 2
5
0 = Blocked
1 = Start enable FWD
0 = Blocked
1 = Start enable REV
0 = Selected setpoint source
1 = Fixed frequency 1 (P-20)
Setpoint value
AI1
Connection of DI1 and DI2
leads to a quick stop (P-24).
6
0 = Blocked
1 = Start enable
0 = FWD
1 = REV
External fault:
0 = Fault
1 = Enable
Setpoint value
AI1
Connection of an external
thermistor of type PT100 or
similar to DI3
7
0 = Blocked
1 = Start enable FWD
0 = Blocked
1 = Start enable REV
External fault:
0 = Fault
1 = Enable
Setpoint value
AI1
Connection of DI1 and DI2
leads to a quick stop (P-24).
8
0 = Blocked
1 = Start enable
0 = FWD
1 = REV
DI3/AI2
AI1/DI4
Fixed frequency
0
0
FF1 (P-20)
1
0
FF2 (P-21)
0
1
FF3 (P-22)
1
1
FF4 (P-23)
9
0 = Blocked
1 = Start enable FWD
0 = Blocked
1 = Start enable REV
DI3/AI2
AI1/DI4
Fixed frequency
Connection of DI1 and DI2
leads to a quick stop (P-24).
0
0
FF1 (P-20)
1
0
FF2 (P-21)
0
1
FF3 (P-22)
1
1
FF4 (P-23)
10
1 = Run FWD
0 = Stop
0 = Selected setpoint source
1 = Fixed frequency 1 (P-20)
Setpoint value
AI1
11
1 = Run FWD
0 = Stop
1 = Run REV
Setpoint value
AI1
Connection of DI1 and DI2
leads to a quick stop (P-24).
12
0 = Blocked
1 = Start enable FWD
0 = Quick stop (P-24)
1 = Run FWD
0 = Selected setpoint source
1 = Fixed frequency 1 (P-20)
Setpoint value
AI1
Note:
negative fixed frequencies are inverted it Run REV is selected.
Summary of Contents for PowerXL DX-NET-SWD
Page 4: ...II ...
Page 10: ...0 About this Manual 0 6 Units 6 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 16: ...1 Device series 1 7 Disposal 12 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 26: ...3 Installation 3 4 Dismantling 22 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 64: ...4 Commissioning 4 5 SmartWire DT diagnostics 60 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 68: ...5 Appendix 5 2 SmartWire DT 64 DX NET SWD 06 13 MN04012009Z EN www eaton com ...