Appendix E—STO function
POWERXL SERIES VFDS
MN040060EN—September 2020 www.eaton.com
Environmental and EMC conditions
Environmental
Mains supply
system
TN, TT and IT systems (including corner-earthed system)
Overvoltage
Overvoltage category III
Pollution
degree
Pollution degree 2
Ambient
operating
temperature
-10°C to +40°C rated VT (variable torque) (110% OL for 1 min per
10 mins)
-10°C to +50°C rated CT (constant torque) (150% OL for 1 min
per 10 mins)
Up to +60°C with derating
Cold weather function can be enabled to extend the lower range
to -20°C
Storage
temperature
–40 °F (–40 °C) to 158 °F (70 °C)
Relative
humidity
0 to 95% RH, non-condensing, non-corrosive, no directly dripping
Altitude
100% load capacity (no derating) up to 1,000m; 1% derating for
each 100m up to 2,000m (UL listing); up to 4,000m (without UL
listing)
Vibration
IEC 60068-2-6
Power supply connected (no package)
Keyhole mounting and DIN rail mounting
Sinusoidal motion
10 Hz ≤ f ≤57 Hz: 0.075 mm amplitude
57 Hz > f ≤ 150 Hz: 1g
1oct/min, 10 sweep cycles per axis on each of 3 mutually
perpendicular axes
Shock
IEC 60068-2-27
Power supply connected (no package)
Keyhole mounting and DIN Rail mounting
Half sine pulse motion
Peak acceleration 15g with duration 11ms
Total 18 shocks for 3 mutually perpendicular axes and 6
directions
Enclosure class IP20 / UL open type
IP20 / NEMA 1 / UL Type 1 with NEMA 1 kit installed
EMC
Immunity
EN 61800-3:2004+A1:2012, IEC 61800-3:2017, 2nd environment,
IEC 61800-5-2:2016, IEC/EN 61326-3-1:2017
Radiated
emissions
EN 61800-3:2004+A1:2012, IEC 61800-3:2017, 2nd environment,
Category 2
Conducted
emissions
EN 61800-3:2004+A1:2012, IEC 61800-3:2017, 2nd environment,
Category 2
INFORMATION
External filter shall be used for non-EMI version drives to
keep CE EMC compliance. Refer to installation manual for
detailed information of external filter. If an external filter
type other than recommended in the manual is used, the
CE EMC compliance shall be reconfirmed first. Please
contact the factory or your local Eaton sales representative
if necessary.
Applicable standards
IEC 61800-5-2:2016
Adjustable speed electrical power drive systems
Part 5-2: Safety requirements—functional
IEC 61800-5-1: 2007+A1:2016 (as far as applicable)
Adjustable speed electrical power drive systems
Part 5-1: Safety requirements – Electrical, thermal and energy
IEC 61800-3:2017 (as far as applicable)
Adjustable speed electrical power drive systems
Part 3: EMC requirements and specific test methods
IEC 61326-3-1:2017
Electrical equipment for measurement, control and laboratory use – EMC
requirements
Part 3-1: Immunity requirements for safety-related systems and for equipment
intended to perform safety-related functions (functional safety) – General
industrial applications
IEC 62061:2015
Safety of machinery – Functional safety of safety-related electrical, electronic
and programmable electronic control systems
ISO 13849-1:2015
Safety of Machinery – Safety Related Parts of Control Systems
Part 1: General principles for design
IEC 61508, parts 1-7:2010
Functional safety of electrical/electronic/programmable electronic safety-related
systems
Requirement for installation, commission,
maintenance
A three-pin terminal block in control board (STO in
Figure 32
)
is used for customer to connect emergency stop switch.
When finished the installation, the STO function shall be
verified. Refer to
Figure 33
for the detailed wiring method.
The emergency stop switch for STO shall be closed state
normally.
The STO function shall be verified according to following
steps:
•
Apply main power to DM1.
•
Run the motor and wait until the motor operating stably.
•
Open the switch of STO1 or STO2, both “STO Fault” and
“Safety Torque Off” shall be triggered and the motor shut
down. Fault codes are FC 23 and FC 66.
•
Closed STO1 and STO2 switches.
•
Restart motor and wait until the motor operating stably.
•
Open the switches of STO1 and STO2 at the same time,
only “Safety Torque Off” shall be triggered and the motor
shut down. Fault code is FC 66.
•
Closed STO1 and STO2 switches. Test finished.
otes:
N
•
STO fault indicates two different fault types. One is the
drive internal circuit fault and the other is the case that
two STO input signals are not consistent within 200 ms.
•
If the customer needs more detailed information or the
test result is mismatched, please contact the factory or
your local Eaton sales representative.