52
Appendix B—Installation guidelines
POWERXL SERIES VFDS
MN040060EN—September 2020 www.eaton.com
Table 29. IEC cable and fuse sizes (continued).
Output rating
Input rating
IEC application
Input
voltage
Frame
size
Drive
catalog
number
CT/I
H
current
amps
VT/I
L
current
amps
CT/I
H
current
amps
VT/I
L
current
amps
Recom
mended
fuse
(max
rating)
100 kAIC
Recom-
mended
miniature
circuit
breaker
(max
rating)
10/14
kAIC
Recom-
mended
Type E
CMC
(max.
rating)
65 kAIC
Recom-
mended
circuit
breaker
(max
rating)
100
kAIC
(open
type
only for
3-phase)
IEC
cable
size
line
and
motor
mm
2
IEC
cable
size
ground
mm
2
Term-
inal
size
line
and
motor
mm
2
Term-
inal
size
ground
mm
2
100 Vac
to 120
Vac
50/60
Hz
1-phase
FR1
DM1-
111D6…
1.6
2.5
6.4
10
30
30
\
30
2.5
2.5
0.2-6
1-6
DM1-
113D0…
3
4.8
13.5
20
70
63
\
70
6
6
0.2-6
1-6
FR2
DM1-
114D8…
4.8
6.9
20
26.4
90
63
\
90
10
10
0.5-16
1-10
DM1-
116D9…
6.9
7.8
26.4
30
125
63
\
125
10
10
0.5-16
1-10
200 Vac
to 240
Vac
50/60
Hz
1-phase
FR1
DM1-
121D6…
1.6
2.5
4
6.5
15
15
\
15
2.5
2.5
0.2-6
1-6
DM1-
123D0…
3
4.8
8
11
30
30
\
30
2.5
2.5
0.2-6
1-6
DM1-
124D8…
4.8
7.8
11
17
60
63
\
60
6
6
0.2-6
1-6
FR2
DM1-
127D8…
7.8
11
18
23
80
63
\
80
6
6
0.5-16
1-10
DM1-
12011…
11
17.5
23
35
125
63
\
125
10
10
0.5-16
1-10
FR3
DM1-
12017…
17.5
25.3
38
49.6
200
\
\
200
16
16
0.5-16
1.5-6
200 Vac
to 240
Vac
50/60
Hz
3-phase
FR1
DM1-
321D6…
1.6
2.5
2.1
3.3
6
5
6.3
15
2.5
2.5
0.2-6
1.5-6
DM1-
323D0…
3
4.8
3.9
5.8
15
10
6.3
15
2.5
2.5
0.2-6
1.5-6
DM1-
324D8…
4.8
7.8
5.8
9.4
20
15
10
15
2.5
2.5
0.2-6
1.5-6
DM1-
327D8…
7.8
11
9.4
13.2
30
20
16
20
4
4
0.2-6
4-10
FR2
DM1-
32011…
11
17.5
12.7
20.1
40
30
25
30
6
6
0.5-16
4-10
DM1-
32017…
17.5
25.3
20.1
29.1
60
40
32
45
10
10
0.5-16
6-10
FR3
DM1-
32025…
25.3
32.2
29.1
37
70
50
40
50
10
10
0.5-16
10-16
FR4
DM1-
32032…
32.2
48.3
35.4
53.1
100
\
\
80
25
16
0.5-35
10-16
DM1-
32048…
48.3
62.1
53.1
68.3
125
\
\
100
35
16
0.5-35