34
Chapter 5—Electrical installation
POWERXL SERIES VFDS
MN040060EN—September 2020 www.eaton.com
Table 20. Connection sizes and torques
.
Output rating
Size and torque
Input voltage
Frame
size
Drive
catalog
number
CT/I
H
current
amps
VT/I
L
current
amps
Power
wire size
AWG
(mm
2
)
Power wire
torque
in.-lb (N·m)
Ground
wire size
AWG
(mm
2
)
Ground
wire
torque
in.-lb (N·m)
Control
wire size
AWG (mm
2
)
Control
wire torque
in.-lb (N·m)
AI/DI
RO
200 Vac to
240 Vac
50/60 Hz
3-phase
FR1
DM1-321D6… 1.6
2.5
14 (2.5)
4.4 (0.5)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-323D0… 3
4.8
14 (2.5)
4.4 (0.5)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-324D8… 4.8
7.8
14 (2.5)
4.4 (0.5)
12 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-327D8… 7.8
11
12 (4)
4.4 (0.5)
10 (4)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR2
DM1-32011… 11
17.5
10 (6)
10.5 (1.2)
10 (6)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-32017… 17.5
25.3
8 (10)
10.5 (1.2)
10 (10)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR3
DM1-32025… 25.3
32.2
8 (10)
10.5 (1.2)
8 (10)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR4
DM1-32032… 32.2
48.3
4 (25)
33 (3.73)
8 (16)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-32048… 48.3
62.1
3 (35)
33 (3.73)
6 (16)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
380 Vac to
480 Vac
50/60 Hz
3-phase
FR1
DM1-341D5… 1.5
2.2
14 (2.5)
4.4 (0.5)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-342D2… 2.2
4.3
14 (2.5)
4.4 (0.5)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-344D3… 4.3
5.6
14 (2.5)
4.4 (0.5)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-345D6… 5.6
7.6
14 (2.5)
4.4 (0.5)
10 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR2
DM1-347D6… 7.6
12
12 (4)
10.5 (1.2)
10 (4)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-34012… 12
16
10 (6)
10.5 (1.2)
10 (6)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-34016… 16
23
8 (10)
10.5 (1.2)
10 (10)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR3
DM1-34023..
23
31
8 (10)
10.5 (1.2)
8 (10)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR4
DM1-34031… 31
38
6 (16)
33 (3.73)
8 (16)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-34038… 38
46
4 (25)
33 (3.73)
8 (16)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
525 Vac to
600 Vac
50/60 Hz
3-phase
FR2
DM1-354D5… 4.5
7.5
-
-
-
-
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-357D5… 7.5
10
-
-
-
-
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-35010… 10
13.5
-
-
-
-
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR3
DM1-35013… 13.5
18
-
-
-
-
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR4
DM1-35018… 18
22
-
-
-
-
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-35022… 22
27
-
-
-
-
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
Notes:
Line and motor cable size is selected according to UL 61800-5-1 for copper conductor rated 75°C. Use only with copper wire rated 75°C here. Size requirements for
other different wire types are defined in the National Electrical Code
®
, ANSI/NFPA
®
70.
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL 61800-5-1.
If power cubes or bypass are used, a UL listed Class J, T, CF, CC or equivalent fuse is recommended.
(continued).