37
Chapter 5—Electrical installation
POWERXL SERIES VFDS
MN040060EN—September 2020 www.eaton.com
Table 22. International cable and fuse sizes
.
IEC cable and fuse sizes
Output rating
Input rating
IEC application
Input
voltage
Frame
size
Catalog
number
CT/I
H
current
amps
VT/I
L
current
amps
CT/I
H
current
amps
VT/I
L
current
amps
Recom-
mended
fuse
(max.
rating)
100
kAIC
Recom-
mended
miniature
circuit
breaker
(max.
rating)
10/14
kAIC
Recom-
mended
Type E
CMC
(max.
rating)
65 kAIC
Recom-
mended
circuit
breaker
(max.
rating)
100 kAIC
(Open
type only
for
3-phase)
IEC
cable
size
line
and
motor
mm
2
IEC
cable
size
ground
mm
2
Terminal
size
line and
motor
mm
2
Terminal
size
ground
mm
2
100 Vac
to
120 Vac
50/60
Hz
1-phase
FR1
DM1-111D6 1.6
2.5
6.4
10
30
30
\
30
2.5
2.5
0.2-6
1-6
DM1-113D0 3
4.8
13.5
20
70
63
\
70
6
6
0.2-6
1-6
FR2
DM1-114D8 4.8
6.9
20
26.4
90
63
\
90
10
10
0.5-16
1-10
DM1-116D9 6.9
7.8
26.4
30
125
63
\
125
10
10
0.5-16
1-10
200 Vac
to
240 Vac
50/60
Hz
1-phase
FR1
DM1-121D6 1.6
2.5
4
6.5
15
15
\
15
2.5
2.5
0.2-6
1-6
DM1-123D0 3
4.8
8
11
30
30
\
30
2.5
2.5
0.2-6
1-6
DM1-124D8 4.8
7.8
11
17
60
63
\
60
6
6
0.2-6
1-6
FR2
DM1-127D8 7.8
11
18
23
80
63
\
80
6
6
0.5-16
1-10
DM1-12011 11
17.5
23
35
125
63
\
125
10
10
0.5-16
1-10
FR3
DM1-12017 17.5
25.3
38
49.6
200
\
\
200
16
16
0.5-16
1-16
200 Vac
to
240 Vac
50/60
Hz
3-phase
FR1
DM1-321D6 1.6
2.5
2.1
3.3
6
5
6.3
15
2.5
2.5
0.2-6
1.5-6
DM1-323D0 3
4.8
3.9
5.8
15
10
6.3
15
2.5
2.5
0.2-6
1.5-6
DM1-324D8 4.8
7.8
5.8
9.4
20
15
10
15
2.5
2.5
0.2-6
1.5-6
DM1-327D8 7.8
11
9.4
13.2
30
20
16
20
4
4
0.2-6
1.5-6
FR2
DM1-32011 11
17.5
12.7
20.1
40
30
25
30
6
6
0.5-16
4-10
DM1-32017 17.5
25.3
20.1
29.1
60
40
32
45
10
10
0.5-16
4-10
FR3
DM1-32025 25.3
32.2
29.1
37
70
50
40
50
10
10
0.5-16
6-10
FR4
DM1-32032 32.2
48.3
35.4
53.1
100
\
\
80
25
16
0.5-35
10-16
DM1-32048 48.3
62.1
53.1
68.3
125
\
\
100
35
16
0.5-35
10-16
380 Vac
to
480 Vac
50/60
Hz
3-phase
FR1
DM1-341D5 1.5
2.2
1.8
2.6
6
4
6.3
15
2.5
2.5
0.2-6
1.5-6
DM1-342D2 2.2
4.3
2.6
5.2
10
8
6.3
15
2.5
2.5
0.2-6
1.5-6
DM1-344D3 4.3
5.6
5.2
6.7
15
10
10
15
2.5
2.5
0.2-6
1.5-6
DM1-345D6 5.6
7.6
6.7
9.1
30
15
10
15
2.5
2.5
0.2-6
1.5-6
FR2
DM1-347D6 7.6
12
9.1
14.4
30
20
16
20
4
4
0.5-16
4-10
DM1-34012 12
16
14.4
19.2
40
25
25
30
6
6
0.5-16
4-10
DM1-34016 16
23
19.2
27.6
60
32
32
40
10
10
0.5-16
4-10
FR3
DM1-34023 23
31
26.5
35.7
70
\
40
50
10
10
0.5-16
6-10
FR4
DM1-34031 31
38
35.7
43.7
70
\
50
70
16
16
0.5-35
10-16
DM1-34038 38
46
43.7
52.9
80
\
58
80
25
16
0.5-35
10-16
525 Vac
to
600 Vac
50/60
Hz
3-phase
FR2
DM1-354D5 4.5
7.5
DM1-357D5 7.5
10
DM1-35010 10
13.5
FR3
DM1-35013 13.5
18
FR4
DM1-35018 18
22
DM1-35022 22
27
Notes:
Line and motor cable size is selected according to IEC 60364-5-52 for copper conductor with PVC insulation with a wiring condition of ambient temperature 30°C
in air and an installation method of “B2” (cables in conduit and cable trunking systems). For other wiring conditions, please refer to the standard of IEC 60364-5-
52:2009 or suitable cable sizes.
Earthing conductor size is determined by the cross-sectional area of phase conductors according to IEC/EN 61800-5-1. So if phase conductor size is changed,
earthing conductor size should also be changed accordingly.
If power cubes or bypass are used, a class gG/gL fuse is recommended.