Appendix D—Safety Instructions for UL and cUL
DG1 Series VFD
MN040002EN—March 2014
www.eaton.com
67
●
For 230V Drive Series, required line and motor wire torque,
type and size range are listed in
Table 42
Table 42. Required Line and Motor Wire Torque (230V)
Note
1
The line and motor wire size for DG1-32088xx-xxxx can only be 1/0 AWG.
Grounding
●
For 400V Drive Series, required grounding wire torque,
type and size range are listed in
Table 43
Table 43. Required Line and Motor Wire Torque (400V)
Catalog
Number
Terminal Type
Required
Torque
(in-lb)
Required
Wire
Range
FR1
DG1-323D7xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
12.1
14–10 AWG
DG1-324D8xx-xxxx
12.1
14–10 AWG
DG1-326D6xx-xxxx
12.1
14–10 AWG
DG1-327D8xx-xxxx
12.1
14–10 AWG
DG1-32011xx-xxxx
12.1
12–10 AWG
FR2
DG1-32012xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
15.6
10–6 AWG
DG1-32017xx-xxxx
15.6
8–6 AWG
DG1-32025xx-xxxx
15.6
8–6 AWG
FR3
DG1-32031xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
40
6–2 AWG
DG1-32048xx-xxxx
40
4–2 AWG
FR4
DG1-32061xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
95
3–1/0 AWG
DG1-32075xx-xxxx
95
2–1/0 AWG
DG1-32088xx-xxxx
95
1/0 AWG
1
FR5
DG1-32114xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
354
3/0 AWG–
350 kcmil
DG1-32143xx-xxxx
354
4/0 AWG–
350 kcmil
DG1-32170xx-xxxx
354
300–350 kcmil
All Frames Sizes (FR1–FR5)
All models
Control terminal
block
4.5
28~12 (Sol) AWG
30~12 (Str) AWG
Catalog
Number
Terminal Type
Required
Torque
(in-lb)
Required
Wire
Range
FR1
DG1-342D2xx-xxxx
Grounding terminal 10
14–10 AWG
DG1-343D3xx-xxxx
10
14–10 AWG
DG1-344D3xx-xxxx
10
14–10 AWG
DG1-345D6xx-xxxx
10
14–10 AWG
DG1-347D6xx-xxxx
10
14–10 AWG
DG1-349D0xx-xxxx
10
14–10 AWG
FR2
DG1-34012xx-xxxx
Grounding terminal 10
12–6 AWG
DG1-34016xx-xxxx
10
10–6 AWG
DG1-34023xx-xxxx
10
10–6 AWG
FR3
DG1-34031xx-xxxx
Grounding terminal 10
10–4 AWG
DG1-34038xx-xxxx
10
10–4 AWG
DG1-34046xx-xxxx
10
8–4 AWG
FR4
DG1-34061xx-xxxx
Grounding terminal 14
8–1/0 AWG
DG1-34072xx-xxxx
14
6–1/0 AWG
DG1-34087xx-xxxx
14
6–1/0 AWG
FR5
DG1-34105xx-xxxx
Grounding terminal 35
6 AWG–
250 kcmil
DG1-34140xx-xxxx
35
6 AWG–
250 kcmil
DG1-34170xx-xxxx
35
4 AWG–
250 kcmil
Summary of Contents for PowerXL DG1-32011FB-C21C
Page 1: ...PowerXL DG1 Series VFD Installation Manual Effective March 2014 New Information ...
Page 2: ......
Page 83: ......