Appendix A—Technical Data and Specifications
44
DG1 Series VFD
MN040002EN—March 2014
www.eaton.com
Appendix A—Technical Data and Specifications
Table 28. PowerXL Series—DG1
Attribute
Description
Specification
Input ratings
Input voltage Uin
208V to 240V, 380V to 500V, 525V to 600V, –15 to 10%
Input frequency
50 Hz to 60 Hz (variation up to 45 Hz to 66 Hz)
Connection to power
Once per minute or less
Starting delay
3 s (FR1 to FR2), 4 s (FR3), 5 s (FR4), 6 s (FR5)
Short-circuit withstand rating
100 kAIC
Output ratings
Output voltage
0 to Uin
Continuous output current
IL: ambient temperature maximum 40°C, up to 60°C with derating, overload 1.1 x IL (1 min./10 min.)
IH: ambient temperature maximum 50°C, up to 60°C with derating, overload 1.5 x IH (1 min./10 min.)
Overload current
150% respectively 110% (1 min./10 min.)
Initial output current
200% (2 s/20 s)
Output frequency
0–400 Hz (standard)
Frequency resolution
0.01 Hz
Control characteristics
Control methods
Frequency control
Speed control
Open-loop speed control
Open-loop torque control
Switching frequency
Range:
FR1–3: 1 kHz to 12 kHz
FR4–5: 1 kHz to 10 kHz
Defaults:
FR1–3: 4 kHz (IH), 6 kHz (IL)
FR4–5: 3.6 kHz
Automatic switching frequency derating in case of overload.
Frequency reference
Analog input: resolution 0.1% (10-bit), ac1%
Panel reference: resolution 0.01 Hz
Field weakening point
20 Hz to 400 Hz
Acceleration time
0.1 s to 3000 s
Deceleration time
0.1 s to 3000 s
Braking torque
DC brake: 30% x Motor Rated Torque (Tn) (without brake chopper)
Dynamic braking (with optional brake chopper using an external brake resistor):
100% continuous maximum rating
Ambient conditions
Ambient operating temperature
–10°C (no frost) to +50°C, up to +60°C with derating (CT)
–10°C (no frost) to +40°C, up to +55°C with derating (VT)
Storage temperature
–40°C to +70°C
Relative humidity
0–95% RH, noncondensing, non-corrosive
Air quality:
●
Chemical vapors
●
Mechanical particles
Tested according to IEC 60068-2-60 Test Key:
Flowing mixed gas corrosion test, Method 1 (H2S [hydrogen sulfide] and SO2 [sulfur dioxide])
Designed according to:
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S2
Altitude
100% load capacity (no derating) up to 3280 ft (1000 m); 1% derating for each 328 ft (100 m) above
3280 ft (1000 m); max. 9842 ft (3000 m) (2000 m for corner grounded earth main systems)
Vibration:
●
EN 61800-5-1
●
EN 60668-2-6
5–150 Hz
Displacement amplitude: 1 mm (peak) at 5 Hz to 15.8 Hz (FR1–FR5)
Maximum acceleration amplitude: 1g at 15.8 Hz to 150 Hz (FR1–FR5)