Appendix D—Safety Instructions for UL and cUL
68
DG1 Series VFD
MN040002EN—March 2014
www.eaton.com
●
For 230V Drive Series, required grounding wire torque,
type and size range are listed as below:
Table 44. Required Line and Motor Wire Torque (230V)
Catalog
Number
Terminal Type
Required
Torque
(in-lb)
Required
Wire
Range
FR1
DG1-323D7xx-xxxx
Grounding terminal 10
14–10 AWG
DG1-324D8xx-xxxx
10
14–10 AWG
DG1-326D6xx-xxxx
10
14–10 AWG
DG1-327D8xx-xxxx
10
14–10 AWG
DG1-32011xx-xxxx
10
14–10 AWG
FR2
DG1-32012xx-xxxx
Grounding terminal 10
12–6 AWG
DG1-32017xx-xxxx
10
10–6 AWG
DG1-32025xx-xxxx
10
10–6 AWG
FR3
DG1-32031xx-xxxx
Grounding terminal 10
10–4 AWG
DG1-32048xx-xxxx
10
10–4 AWG
FR4
DG1-32061xx-xxxx
Grounding terminal 14
8–1/0 AWG
DG1-32075xx-xxxx
14
6–1/0 AWG
DG1-32088xx-xxxx
14
6–1/0 AWG
FR5
DG1-32114xx-xxxx
Grounding terminal 35
6 AWG–
250 kcmil
DG1-32143xx-xxxx
35
6 AWG–
250 kcmil
DG1-32170xx-xxxx
35
4 AWG–
250 kcmil