Appendix D—Safety Instructions for UL and cUL
66
DG1 Series VFD
MN040002EN—March 2014
www.eaton.com
●
230V Drive Series are suitable for use on a circuit capable
of delivering not more than 100,000 rms symmetrical
amperes, 240 volts maximum when protected by UL and
cUL/CSA Recognized Class T fuse with an A.I.C. rating of
100 kA minimum. Refer to the following information for
recommended fuse ratings. See
Table 40
.
Table 40. Fuse Ratings—230V Drive Series
Field Wiring
●
The field installed conductors for this drive should be 75°C
copper wire only
●
The enclosure openings provided for conduit connections
in the field shall be closed by UL Listed conduit fittings
with same type rating as the enclosure (Type 1/Type 12)
Line and Motor Wiring
●
For 400V Drive Series, required line and motor wire torque,
type and size range are listed in
Table 41
Table 41. Required Line and Motor Wire Torque (400V)
Frame Size
Catalog
Number
Fuse Rating
1
DG1-323D7xx-xxxx
600V, 10A
DG1-324D8xx-xxxx
600V, 10A
DG1-326D6xx-xxxx
600V, 10A
DG1-327D8xx-xxxx
600V, 15A
DG1-32011xx-xxxx
600V, 15A
2
DG1-32012xx-xxxx
600V, 20A
DG1-32017xx-xxxx
600V, 30A
DG1-32025xx-xxxx
600V, 35A
3
DG1-32031xx-xxxx
600V, 60A
DG1-32048xx-xxxx
600V, 80A
4
DG1-32061xx-xxxx
600V, 100A
DG1-32075xx-xxxx
600V, 110A
DG1-32088xx-xxxx
600V, 125A
5
DG1-32114xx-xxxx
600V, 175A
DG1-32143xx-xxxx
600V, 200A
DG1-32170xx-xxxx
600V, 250A
Catalog
Number
Terminal Type
Required
Torque
(in-lbs)
Required
Wire
Range
FR1
DG1-342D2xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
5–7
14–10 AWG
DG1-343D3xx-xxxx
5–7
14–10 AWG
DG1-344D3xx-xxxx
5–7
14–10 AWG
DG1-345D6xx-xxxx
5–7
14–10 AWG
DG1-347D6xx-xxxx
5–7
14–10 AWG
DG1-349D0xx-xxxx
5–7
14–10 AWG
FR2
DG1-34012xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
15.6
12–6 AWG
DG1-34016xx-xxxx
15.6
10–6 AWG
DG1-34023xx-xxxx
15.6
8–6 AWG
FR3
DG1-34031xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
40
8–2 AWG
DG1-34038xx-xxxx
40
6–2 AWG
DG1-34046xx-xxxx
40
4–2 AWG
FR4
DG1-34061xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
95
4–1/0 AWG
DG1-34072xx-xxxx
95
3–1/0 AWG
DG1-34087xx-xxxx
95
1–1/0 AWG
FR5
DG1-34105xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
354
2/0 AWG–
350 kcmil
DG1-34140xx-xxxx
354
3/0 AWG–
350 kcmil
DG1-34170xx-xxxx
354
250–350 kcmil
All Frames Sizes (FR1–FR5)
All models
Control terminal
block
4.5
28~12 (Sol) AWG
30~12 (Str) AWG