6 Parameters
6.3 Operational data indicator
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
137
P-00 - Display values
P00-01
20
ro
%
Analog input 1
100 % = Maximum input voltage
P00-02
21
ro
%
Analog input 2
100 % = Maximum input voltage
P00-03
23
ro
Hz/rpm
Frequency reference value / Motor shaft speed
Shown in Hz if P-10 = 0;
otherwise shown in rpm
P00-04
11
ro
State
DI1, DI2, DI3,
DI4
Digital inputs 1 - 4
State of the frequency inverter's digital input
P00-05
ro
0
reserved
P00-06
ro
0
reserved
P00-07
ro
V
Motor voltage: the value of the rms voltage being applied at the motor
P00-08
23
ro
V
Internal DC bus voltage
P00-09
24
ro
°C
Unit Temperature
Heatsink temperature in °C
P00-10
ro
HH:MM:SS
The frequency inverter's operating time
Not affected when the parameters are reset to their default settings.
P00-11
ro
HH:MM:SS
The frequency inverter's operating time since the last trip (1)
Operating time clock stopped by frequency inverter lockup (or trip). Reset
with next enable only if a trip occurred. Also reset with next enable after
the frequency inverter's mains power is switched off.
P00-12
ro
HH:MM:SS
The frequency inverter's operating time since the last trip (2)
Operating time clock stopped by frequency inverter lockup (or trip). Reset
with next enable only if a trip occurred (undervoltage does not count as a
trip) – Not reset when mains power is switched off/on unless a trip
occurred before the mains power was switched off.
P00-13
ro
HH:MM:SS
The frequency inverter
’
s operating time since the last lockup
The frequency inverter
’
s operating time clock was stopped with the
lockup.
→
Reset the value with next enable.
P00-14
ro
4 - 32 kHz
Pulse frequency
The frequency inverter
’
s actual rms output pulse frequency. If the
frequency inverter is too hot, this value may be lower than the frequency
selected in P-17. The frequency inverter will automatically reduce the
pulse frequency in order to prevent an excess temperature trip and main-
tain operation.
P00-15
ro
0 - 1000 V
DC bus voltage log (256 ms)
The eight most recent values before the trip
Updated every 250 ms.
P00-16
ro
-20 - 120 °C
Log for thermistor temperature
The eight most recent values before the trip
Updated every 500 ms.
PNU
ID
Access rights
Value
Description
DS
RUN
ro/rw
Summary of Contents for PowerXL DC1
Page 1: ...Manual PowerXL DC1 Frequency Inverter 10 12 MN04020003Z EN...
Page 4: ...II...
Page 12: ...0 About this manual 0 5 Units 8 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Page 190: ...9 Appendix 9 9 Sinusoidal filter 186 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...