6 Parameters
6.2 Digital and analog inputs
122
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
P-31
159
✓
rw
REAF, Start function with automatic restart, operating unit
1
This parameter will only be active if the keypad control operating mode
is being used (P-12 = 1 or P-12 = 2).
0
Minimum speed; keypad
The keypad’s start and stop pushbuttons are enabled, and control
signal terminals 1 and 2 must be connected.
The frequency inverter will always start with the minimum frequency/
speed (P-02).
1
Previous speed, keypad
The keypad’s start and stop pushbuttons are enabled; control signal
terminals 1 and 2 must be connected.
The frequency inverter will always start with the most recent operating
frequency/speed.
2
Minimum speed; terminal
The frequency inverter will be started directly from the control signal
terminals; the keypad's start and stop buttons will be ignored.
The frequency inverter will always start with the minimum frequency/
speed (P-02).
3
Previous speed, terminal
PNU
ID
Access rights
Value
Description
DS
RUN
ro/rw