3 Installation
3.4 Electrical Installation
70
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
3.4.2 Connection on control section
The 11-terminal control terminal block is a plug-in block and is located on the
front.
Figure 41:
Location of plug-in control signal terminals
The control cables should be screened and twisted. The screening is applied
on one side in the proximity of the frequency inverter (PES).
Figure 42:
Prevent the shield from becoming unbraided
Alternatively, in addition to the broad area gland plate, you can also twist the
screen braid at the end and connect to the protective earth with a cable lug.
To prevent EMC disturbance, this twisted shielding connection should be
made as short as possible (
Prevent the screen from becoming unbraided at the other end of the control
cable, e.g. by using a rubber grommet. The shield braid must not make any
connection with the protective ground here because this would cause prob-
lems with an interference loop.
→
Prevent the screening from becoming unbraided, i.e. by pushing
the separated plastic covering over the end of the shielding or
with a rubber grommet on the end of the screening.
1 2 3 4 5 6 7 8 9 10 11
15 mm
(0.59’
’)
PES