
6 Parameters
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
99
P-30
158
✓
rw
REAF, Start function with automatic restart, control signal terminals
Ed9E-r
Used to define the frequency inverter's behavior concerning the enable
digital input and to configure the automatic restart function.
Ed9E-r
disabled
After being switched on, as well as after a reset, the frequency inverter
will not start if digital input 1 remains closed (the frequency inverter
will need a new start edge). The input must be closed after switching
on, as well as after a reset, in order to start the frequency inverter.
AVto-0
The frequency inverter will start automatically.
(The frequency inverter will not need a start edge; the signal will
continue to be applied.)
After being switched on, as well as after a reset, the frequency inverter
will start automatically if digital input 1 is closed.
AVto-1
The frequency inverter will start automatically once.
After a trip, the frequency inverter will make up to five attempts to
restart at 20-second intervals.
The frequency inverter must be de-energized in order to reset the
counter. The number of restart attempts is counted. If the frequency
inverter does not start after the last attempt, it will switch to an error
condition and request the user to reset the error manually.
AVto-2
The frequency inverter will start automatically twice.
AVto-3
The frequency inverter will start automatically three times.
AVto-4
The frequency inverter will start automatically four times.
AVto-5
The frequency inverter will start automatically five times.
P-31
159
✓
rw
REAF, Start function with automatic restart, operating unit
1
This parameter will only be active if the keypad control operating mode
is being used (P-12 = 1 or P-12 = 2).
0
Minimum speed; keypad
The keypad’s start and stop buttons are enabled, and control signal
terminals 1 and 2 must be connected.
The frequency inverter will always start with the minimum frequency/
speed (P-02).
1
Previous speed, keypad
The keypad
’
s start and stop buttons are enabled; control signal termi-
nals 1 and 2 must be connected. The frequency inverter will always
start with the most recent operating frequency/speed.
2
Minimum speed; terminal
The frequency inverter will be started directly from the control signal
terminals; the keypad
’
s start and stop buttons will be ignored.
The frequency inverter will always start with the minimum frequency/
speed (P-02).
3
Previous speed, terminal
PNU
ID
Access rights
Value
Description
DS
RUN
ro/rw
Summary of Contents for PowerXL DC1
Page 1: ...Manual PowerXL DC1 Frequency Inverter 10 12 MN04020003Z EN...
Page 4: ...II...
Page 12: ...0 About this manual 0 5 Units 8 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Page 190: ...9 Appendix 9 9 Sinusoidal filter 186 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...