Operation
Eaton 9135 5000/6000 VA UPS User’s Guide 164201726—Rev 4
www.eaton.com/powerquality
35
Access to Maintenance
To access the Maintenance menu:
1.
Scroll to the Maintenance menu by pressing the button.
2.
Press the
button to access the menu.
Figure 29. Access to Maintenance
Table 7. On and Off Settings
Function
Factory Setting
Options
Comments
Cold Start
Disable
Enable
Start on battery
Forced Reboot
Enable
Enables automatic restart of the system even if
utility power is restored before the end of the
shutdown sequence
Auto Restart
Enable
Disable
UPS restarts automatically when utility power is
restored
Energy Saving
Disable
Enable
Automatic shutdown on battery if output load level
<10%
Sleep Mode
Enable
Disable
Remote Command
Enable
Disable
Enables consideration of shutdown or restart
orders from software to be authorized
Table 8. Battery Settings
Function
Factory Setting
Options
Comments
Auto Battery Test
Everyweek
No test / everyday /
everyweek /everymonth
Low Batt Warning
20%
0 to 100%
1% increment
User Batt Settings
UPS reads number of battery
modules connected
From 0 to 95 Ah
5 Ah increment
Deep Disch Protect
Yes
No
Protection against deep discharge.
If disabled, the Eaton warranty will be void.
(