2. Quick Start Guide for the Meter
• VTV1 = Line 1 or Va
• VTV2 = Line 2 or Vb
• VTV3 = Line 3 or Vc
• VTV4 = Line 4 or Vn (neutral)
• VTVR = Metering Reference Ground
VX Optional Auxiliary Voltage Connections:
• VXV6 = Line 1’ or Va2
• VXV7 = Line 2’ or Vb2
• VXV8 = Line 3’ or Vc2
CT Terminal Connections:
Current Inputs accepts a 5-amp secondary with available Primary settings of 5-9999, for a
CT ratio of 5:5 to 9999:5. It is strongly recommended that the Current Inputs be connect
-
ed to the Meter by way of a shorting block.
• Line 1 CT connected to Terminals 11 (polarity mark) & 12 (return)
• Line 2 CT connected to Terminals 21 (polarity mark) & 22 (return)
• Line 3 CT connected to Terminals 31 (polarity mark) & 32 (return)
• Neutral CT connected to Terminals 41 (polarity mark) & 42 (return)
• Ground CT connected to Terminals 51 (polarity mark) & 52 (return)
2.7. Establishing Communications between the Meter and the Displays
1. 6-inch color touchscreen display: See TD150015EN (available on the Eaton website,
www.eaton.com/meters) for instructions on how to connect the 6-inch display to the Meter.
2. 12-inch advanced color touchscreen display: See TD150019EN (available on the Eaton
website, www.eaton.com/meters) for instructions on how to connect the 12-inch display to
the Meter.
Figure 3:
CT and VT Connections.
VX Connections
CT Connections
VT Connections