2. Quick Start Guide for the Meter
2.2. Power Supply Connections
1. Connect the Power Supply (PXMPS-1)
The Meter is powered using a 100-240 Vac or 110-250 Vdc (PXMPS-1) standard power
supply.
• PS1-3 connected to ground
• PS1-2 connected to Neutral (Vac) or (-) Vdc
• PS1-1 connected to Line (Vac) or (+) Vdc
Fabricate a power cord of suitable length to connect PS1-1/PS1-2/PS1-3 (refer to
Figure 1) to a suitable Power Source that supplies (100-240 Vac or 110-250 Vdc).
• Power LED should be solid blue ON.
• Health LED should blink green once per second.
• Status LED will blink red if there are unacknowledged events.
Refer to Troubleshooting Section in this manual.
PXMPS-1 Card
Power Supply
Connection
PS1-3
PS1-2
PS1-1
Health &
Status
LEDs
Figure 1:
Meter Power Supply Connection and LED Locations.
Power
LED
Protective Earth
Ground