![background image](http://html1.mh-extra.com/html/eaton/power-xpert-pxm-4000/power-xpert-pxm-4000_quick-start-manual_3699421015.webp)
www.eaton.com
IB02601007E
Page 15
2. Quick Start Guide for the Meter
5. Set the clock by clicking on Settings > Clock > Edit.
Notes on Modbus support:
The Optional Communications Expansion (CE) card also provides communication via
Modbus RTU (CE3 & CE4 - see the User and Installation manual [IM02601004E] for Mod-
bus instructions). The RS485 CE3 port supports Modbus RTU slave to a master monitor-
ing system. The port defaults as a Master Gateway, which relays Ethernet Modbus TCP
command to slave meters connected to the same RS485 link. The Modbus slave address
may be set via the Display or with a web browser.