2. Quick Start Guide for the Meter
2.3. Configure the Security Mode Dip Switches
Figure 2:
Meter’s Dip Switches and Tamper Seals.
Tamper Seals
DIP Switches
ON OFF
DS-1 DS-2 DS-3
OFF OFF
ON is
Normal.
OFF is
Safe
Mode.
No restrictions (user ID/Password re-
quired)
ADMIN/ADMIN accepted for 15 minutes
after boot-up
OFF ON
ON is
Normal.
OFF is
Safe
Mode.
Medium Security - Energy & Demand
resets prohibited
ON
OFF
ON is
Normal.
OFF is
Safe
Mode.
High Security- Configuration changes;
Energy & Demand reset prohibited
ON
ON
ON or
OFF.
Factory Test Mode - The meter should
never be operated in this mode. The meter
will indicate that it’s in factory test mode
through a repeating series of three flashes
on the
red
Status LED