background image

Texmate, Inc. Tel. (760) 598-9899  •  www.texmate.com

DL-40JANUS manual (d0111)

Page 1

•  External transmitters or signal conditioners can be eliminated  

by direct connection of the sensor output to more than 29 Plug-

in Input Signal Conditioners that include: 

  – AC Current   

– Pressure 

– Resistance

  – AC/DC Voltage 

– Process 

– *Temperature 

  – Load Cell 

 

– Prototype 

– 4 to 20 mA 

*See models DL-40-RTD and DL-40-RTD for higher accuracy  

digitally linearized thermocouple and RTD

•  Optional isolated 14 bit analog output. User or factory scalable 

to 4 to 20 mA, 0 to 20 mA or 0 to 10 V across any desired 

  digital span from ± one count to the full scale range of – 1999 

to 9999 (12000 counts).

•  Optional Isolated Modbus RTU RS-485 serial communication 

with selectable baud rate (9600, 19200), address and parity. 

•   Auto-sensing AC/DC power supply. For voltages between 
     

85-265 VAC / 95-370 VDC (PS1) 

or 15-48 VAC / 10-72 VDC (PS2).

•  24 V DC excitation is available to power external transmitters 

and 5 or 10 V DC excitation is available for resistance bridge 

type sensors such as Load Cells and Pressure Transducers.

•  Standard red or optional green or super bright red 4-digit LED 

with display range –1999 to 9999 (12000 counts).

•  Red or green 0.8” LED large display option
•  Four annunciator LEDs provide front panel alarm status  

indication for up to four setpoints.

•  Optional two 9 Amp Form C and two 4 Amp Form A relays, or  

four 4 Amp Form A relays are available.

•  Automatic intelligent averaging smooths noisy signals, while 

providing a fast display response to real input signal changes.

•  Three-button programming from the front panel  

(UP, DOWN and PROGRAM buttons).

•  Front panel selectable four-level brightness control of digital dis-

play, and setpoint LEDs.

•  Four programmable setpoints.
•  Relay activation can be selected to occur above (HI) or below 

(LO) each setpoint.

•  Hysteresis setting for all four setpoints.  Delay on make and 

delay on break for SP1 and SP2.

•  Peak and Valley.  View and Reset.

Auto Calibration Mode . . . . . . . . . . . . 5

Auto Calibration Procedure . . . . . . . . 5

Case Dimensions . . . . . . . . . . . . . . . 16

Connector Pinouts . . . . . . . . . . . 10-11

Controls and Indicators . . . . . . . . . . . 2

Digital Span Selection for Analog

Range Output. . . . . . . . . . . . . . . . . . . 6

Decimal Point & Brightness Selection. . 6

General Features . . . . . . . . . . . . . . . . 1

Glossary of Programming Symbols . . 2

Input Module Analog Calibration . . . . 15

Input Module Component Glossary 14-15

Input Module Calibration . . . . . . 15-16

Input Signal Conditioning Modules . 12-14

Lens Cover & Metal Surround Case 17

Manual Rescaling. . . . . . . . . . . . . . . . 4

Manual Rescaling Procedure. . . . . . . 4

Meter Assembly . . . . . . . . . . . . . . . . 10

Modbus RTU & RS-485 Settings . . . . 7

Modbus RTU Implementation  . . . . . . 7

Modbus Address for DL-40 Registers 8

Ordering Information  . . . . . . . . . . . . 18

Setpoint & Relay Configuration Mode . . . .9

Software Features  . . . . . . . . . . . . . . . 1

Software Logic Tree . . . . . . . . . . . . . . 3

Specifications. . . . . . . . . . . . . . . . . . . 1

Two Point Analog Output Range 

Setting and Calibration. . . . . . . . . . . . 6

0.56" or optional 0.8” large display red or green LED

General Features

Input Module Compatibility

Specifications

Software Features

Index

LEOPARD FAMILY

 

LEOPARD 

A powerful, smart, programmable panel meter  

with optional Modbus RS-485 serial, analog and 

relays output for measurement and control  

applications in a 1/8 DIN 96x48mm case.

DL-40JANUS

With or without an External Signal 

Source for Rescaling

Input Specs:

 ................Depends on Input signal conditioner 

A/D Converter:

 .............14 bit single slope

Accuracy:

 .....................±(0.05% of r 2 counts)

Temp. Coeff.

: ...............100 ppm/°C (Typical)

Warm up time:

 .............2 minutes

Conversion Rate:

 .........5 conversions per second (Typical)

Display:

 ........................4 digit 0.56" Red LED display (std), 0.56” 

or 0.8" Red, Green or Super Bright Red 

(optional)

                                  Range –1999 to 9999 counts. 

Polarity:

 ........................Assumed positive. Displays – negative

Decimal Selection:

 .......Front panel button selectable, X•X•X•X•

Positive Overrange:

 .....Top segments of digital display flash

Negative Overrange:

 ...Bottom segments of digital display flash

Relay Output:

 ..............Two 4 Amp Form A relays and two 9 

Amp Form C, or 4 Amp form A relays. 

Analog Output:

 ............Isolated 14 bit user scalable mA or V

AIC (mA out) ................ 4-20 mA @ 0 to 500Ω max loop resis-

tance.

AIV (volts out) .............. 0-10 V DC @ 500 Ω or higher resistance

Power Supply:

 .............AC/DC Auto sensing wide range supply

PS1 (std)

 ..................... 

85-265 VAC / 95-370 VDC @ 3W max 

3.5W. 50-400Hz.

PS2 .............................. 15-48 VAC / 10-72 VDC @ 2.5W max 

3.5W. 50-400Hz.

Operating Temp.:

 .........0 to 60 °C

Storage Temp:

 .............–20 °C to 70 °C.  

Relative Humidity:

 .......95% (non condensing)

Case Dimensions:

 .......1/8 DIN, Bezel: 96x48 mm (3.78”x1.89”)

                                  Depth behind bezel: 

117 mm  (4.61”)

                                  Plus 11.8 mm (0.47”)  for Right-angled 

connectors, or plus 20 mm (0.79”) for 

Straight-thru connector.

Weight:

 ........................6.5 oz., 8.5 oz when packed

LEOPARD FAMILY:

  More than 29 different  

Plug-in I-Series Input Signal Conditioners are 

approved for Texmate’s Leopard Family of meters. 

Some examples are shown on pages 12 - 14.  

See www.texmate.com for an up to date listing.

Summary of Contents for DL-40JANUS

Page 1: ... 2 Input Module Analog Calibration 15 Input Module Component Glossary14 15 Input Module Calibration 15 16 Input Signal Conditioning Modules 12 14 Lens Cover Metal Surround Case 17 Manual Rescaling 4 Manual Rescaling Procedure 4 Meter Assembly 10 Modbus RTU RS 485 Settings 7 Modbus RTU Implementation 7 Modbus Address for DL 40 Registers8 Ordering Information 18 Setpoint Relay Configuration Mode 9 S...

Page 2: ...by pressing and releasing the or buttons When there are more than two display selec tions they are shown in brackets below the first display and are also selectable by press ing and releasing the or buttons A dotted box indicates these functions are omitted or bypassed when the related hard ware is not present To explain software programming procedures logic diagrams are used to visually assist in...

Page 3: ... POINT AND BRIGHTNESS SELECTION See Page 6 Setpoint 3 SP3 Setpoint 4 SP4 Valley Offset Scale Factor Calibrate Analog Output Lo Calibrate Analog Output Hi X XXX XX XX XXX X XXXX XXXX 2 3 4 Decimal Point dp Display Brightness br TWO POINT ANALOG OUTPUT CALIBRATION SEE PAGE 6 MANUAL RESCALING MODE See Page 4 SELECTION FOR ANALOG RANGE OUTPUT See Page 6 confirm SP4 confirm confirm confirm This menu on...

Page 4: ... STEP B Select Between Calibration of Input or Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 Press the or button to select the display toggling from CAL to inPt 2 Press the P button Display toggles between oFSt and the previous offset setting STEP C Set the Offset on the Digital Display 1 Using the and buttons adjust ...

Page 5: ...Point Analog Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 Press the or button to select the display toggling from CAL to inPt input calibration 2 Press the P button Display toggles between ZErO and the previous zero setting STEP C Set the Meter s Low Input Signal Reading on the Digital Display 1 Apply a zero or low s...

Page 6: ...s the P and buttons at the same time Display toggles between CAL and oFF 2 Press the P button Display shows previous dP selection STEP E Set the Decimal Point 1 Using the and adjust the display to the desired decimal point setting 2 Press the P button Display toggles between br and the previous br setting STEP F Set the Display Brightness 1 Using the and buttons adjust the display to the desired b...

Page 7: ...nts and does not include the deci mal point If you need the decimal value with decimal point you will need to read the register convert it to decimal read 40024 see below to determine decimal location then combine the two Display counts are in Two s Complement notation a Hex values for 0 to 9999 are 0x0000 to 0x270F b Hex values for 1 to 1999 are 0xFFFF to 0xF831 c Over range is indicated by a ret...

Page 8: ...ST2 Setpoint 2 Hysteresis setting 40019 0x0012 SINT16 R W 1999 9999 PRES3 Setpoint 3 setting 40020 0x0013 UINT16 R W 0 9999 HYST3 Setpoint 3 Hysteresis setting 40021 0x0014 SINT16 R W 1999 9999 PRES4 Setpoint 4 setting 40022 0x0015 UINT16 R W 0 9999 HYST4 Setpoint 4 Hysteresis setting 40023 0x0016 UINT16 R W 0 3 RLYMOD Relay activation polarity H L disabled e g HHHH 40024 0x0017 UINT16 R W 0 4 DP ...

Page 9: ...P2 Delay on Make doM Delay Time Setting STEP H Set the SP2 Delay on Break dob Delay Time Setting STEP I Set the Hysteresis Setting for Setpoint 2 1 Using the and buttons adjust the display to the desired hysteresis HYSt value 2 Press the P button Display toggles between SP3 and the previous SP4 setting STEP J Set Setpoint 3 SP3 No doM or dob 1 Using the and buttons adjust the display to the desire...

Page 10: ...16 19 19 18 MANUAL rescaling ON AUTO scaling OFF ON SP1 NO SP1 NO SP2 NO SP2 NO Pins 14 and 15 AC DC Power Input Auto sensing AC DC power supply For voltages between 85 265 V AC 95 370 V DC PS1 or 18 48 V AC 10 72 V DC PS2 Pin 14 AC DC Neutral Neutral power supply line Pin 15 AC DC line Live power supply line Analog and RS 485 Output Board Pins Pins 16 and 17 Analog Output Pin 16 Positive analog o...

Page 11: ...n Isolated 9A Form C Relays 29 28 27 25 26 24 23 22 DL Series Options Order Code OR51 OR52 OR53 OR54 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 Relay Modules with 4 Independent 400V 210mA DC only SSRs 29 28 27 25 26 24 23 22 DL Series Options Order Code OR31 OR32 OR33 OR34 4A 4A 4A 4A 4A 4A 4A 4A 4A 4A SP4 SP3 SP2 SP1 SP1 SP2 SP3 SP4 Relay Modules w...

Page 12: ...n are designed to be header selectable by the user and Texmate s unique WARNING AC and DC input signals and power supply voltages can be hazardous Do Not insert remove or handle modules with live wires connected to any terminal plugs I Series Input Signal Conditioning Modules ID04 DC Amps 5A DC ID09 DC Amps 1A DC DC AMPS LO RANGE HI Increase Span Decrease LEOPARD LYNX TIGER Fully User Scalable 065...

Page 13: ...ble PIN 2 _ 091E I Series Input Signal Conditioning Modules Direct Pressure IGYX IGYY IGYZ Ordering Code Options I G For Single Channel IGYX with two digital inputs the last digit of order code is always X For Universal Direct Pressure IGYZ the last digit of order code is always Z 1 psi Absolute Sensor Range CH1 Order Code CH2 Order Code 1 psi Differential 5 psi Absolute 5 psi Differential 15 psi ...

Page 14: ...les at 25 C J 2 C 1 digit typical J 4 F 1 digit maximum K 3 C 1 digit typical K 5 F 1 digit maximum LEOPARD LYNX TIGER IT01 LINEARITY ZERO SPAN 272D For higher accuracy digitally linearized RTD P385 or P392 and Thermocouples J K R and T see the special Leopard Temperature meters DL 40 RTD and DL 40 RTD which use only two special thermocouple modules which are not compatible with regular Leopard Fa...

Page 15: ...le Calibration Examples LO RANGE HI RANGE 10 SPAN Pot 10 10 10 10 10 Signal Span 20 30 40 50 1 SPAN Adjust Header position Span Adjust Header Span Adjust Header Span Range Header 2 3 4 5 10 10 10 10 10 60 70 80 90 100 1 2 3 4 5 Decrease Span Increase 1 2 3 4 5 Decrease Span Increase 1 2 3 4 5 Equivalent Circuit Acts like a 150 Turn Potentiometer Low Range High Range Input LO Input HI HI LO Increas...

Page 16: ...nd adjust the ZERO pot until the display reads 100 Apply 5 V and check that the display reads 1500 Example C 4 to 20 mA to read 00 0 to 100 0 Signal Span 16 mA Digital Display Span 1000 counts 1 The full scale Signal Span of the Process Input 4 20 mAmodules is 0 to 20 mA for a full scale Digital Display Span of 0 to 2000 counts This will provide a digital display of 1000 counts with an input of on...

Page 17: ...se is made from fire retardant polycar bonate A metal surround case can be ordered to enhance the meter s fire retardant capabilities and also provide shielding against electromagnetic interference EMI The metal case slides over the polycarbonate case and is held firmly in place by spring type non return clips The Metal Surround Case must be factory installed on the polycarbonate case and once ins...

Page 18: ...LED Faceplate NEMA 4 Factory install 76 DL40LG N4 Touch Large Green LED Faceplate NEMA 4 Factory install 76 DL40LR N4 Touch Large Red LED Faceplate NEMA 4 Factory install 76 DL40R N4 Touch Red LED Faceplate NEMA 4 Factory install ART FS S D NRC for artwork set up Faceplate Desc ART FS 001 Install Custom Faceplate per meter 1 color OP MTLCLIP Screw Mounting Clips 2 pc to screw tighten slide bracket...

Reviews: