Technical Data
Effective: May 1998
Page
5
TD.44A.01.T.E
Cutler-Hammer
Magnum DS
Metal-Enclosed
Low-Voltage Switchgear
Ratings
Table R8 – Digitrip Ground Fault Current Pickup Settings
Pickup Settings – Ground Fault Currents (Amperes)
➀
0.25
➁
0.3
➁
0.35
➁
0.4
➁
0.5
➁
0.6
0.75
1.00
Installed
Rating Plug
(Amperes) I
n
200
50
60
70
80
100
120
150
200
250
63
75
88
100
125
150
188
250
300
75
90
105
120
150
180
225
300
400
100
120
140
160
200
240
300
400
600
150
180
210
240
300
360
450
600
800
200
240
280
320
400
480
600
800
1000
250
300
350
400
500
600
750
1000
1200
300
360
420
480
600
720
900
1200
1600
400
480
560
640
800
960
1200
1200
2000
500
600
700
800
1000
1200
1200
1200
2500
600
720
840
960
1200
1200
1200
1200
3000
750
900
1050
1200
1200
1200
1200
1200
3200
800
960
1120
1200
1200
1200
1200
1200
4000
1000
1200
1200
1200
1200
1200
1200
1200
5000
1200
1200
1200
1200
1200
1200
1200
1200
Table R9 – Digitrip Ground Fault Pickup Values
for Secondary Injection Test Kit Amperes
Installed
Rating
Plug
Sensor
Rating
Pickup (Dial) Setting
Values In Secondary Amperes
➀
25%
➁
30%
➁
35%
➁
40%
➁
50%
➁
60%
75%
100%
200
200
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
250
250
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
300
300
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
400
400
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
600
600
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
800
800
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
1000
1000
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
1200
1200
1.25
1.50
1.75
2.00
2.50
3.00
3.75
5.00
1600
1600
1.25
1.50
1.75
2.00
2.50
3.00
3.75
3.75
2000
2000
1.25
1.50
1.75
2.00
2.50
3.00
3.00
3.00
2500
2500
1.25
1.50
1.75
2.00
2.40
2.40
2.40
2.40
3000
3000
1.25
1.50
1.75
2.00
2.00
2.00
2.00
2.00
3200
3200
1.25
1.50
1.50
1.88
1.88
1.88
1.88
1.88
4000
4000
1.25
1.50
1.50
1.50
1.50
1.50
1.50
1.50
5000
5000
1.20
1.20
1.20
1.20
1.20
1.20
1.20
1.20
➀
Tolerance on pickup levels are
±
10% of values
shown in chart.
➁
For Testing Purposes Only: When using an ex-
ternal single-phase current source to test low
level ground fault current settings, it is advis-
able to use the Auxiliary Power Module
(APM). Especially when the single-phase cur-
rent is low, without the APM it may appear as
if the trip unit does not respond until the cur-
rent is well above the set value, leading the
tester to believe there is an error in the trip
unit when there is none. The reason this oc-
curs is that the single-phase test current is not
a good simulation of the normal three-phase
circuit. If three-phase had been flowing, the
trip unit would have performed correctly. Use
the APM for correct trip unit performance
when single-phase tests are made.
www
. ElectricalPartManuals
. com