Technical Data
Effective: May 1998
Page
32
TD.44A.01.T.E
Cutler-Hammer
Magnum DS
Metal-Enclosed
Low-Voltage Switchgear
Application
Table A8 – Heat Loss Data
➂
Estimated Heat Loss Per Breaker (Watts)
MDS-408
MDS-608
MDS-808
MDS-C08
MDS-616
MDS-816
MDS-C16
MDS-620
MDS-820
MDS-C20
MDS-632
MDS-832
MDS-C32
MDS-840
MDS-C40
MDS-850
MDS-C50
➁
➁
➁
➁
➁
➁
➁
➁
➁
➁
➁
➁
➁
➁
➁
➁
➁
➁
Estimated Heat Loss (Watts) Per Structure
➂
Loss is based on the same fully loaded
vertical and cross bus rating in a structure
as given below.
2,000 amperes
698
3,200 amperes
➁
4,000 amperes
➁
5,000 amperes
➁
6,000 amperes
➁
Table A9 – Magnum DS Indoor Switchgear Structure Approximate Weights
(less breakers)
Width
Depth
Pounds (Kilograms)
22-in. (559 mm)
(Breaker Structure)
60 in. (1524 mm)
66 in. (1676 mm)
72 in. (1829 mm)
78 in. (1981 mm)
84 in. (2134 mm)
90 in. (2286 mm)
1250 (568)
1300 (591)
1350 (614)
1400 (636)
1450 (659)
1500 (682)
44-in. (1118 mm)
(Breaker Structure)
60 in. (1524 mm)
66 in. (1676 mm)
72 in. (1829 mm)
78 in. (1981 mm)
84 in. (2134 mm)
90 in. (2286 mm)
2500 (1136)
2600 (1182)
2700 (1227)
2800 (1272)
2900 (1318)
3000 (1364)
22-in. (559 mm)
(Auxiliary Structure)
60 in. (1524 mm)
66 in. (1676 mm)
72 in. (1829 mm)
78 in. (1981 mm)
84 in. (2134 mm)
90 in. (2286 mm)
950 (432)
1000 (455)
1050 (477)
1100 (500)
1150 (523)
1200 (545)
11-in. (279 mm)
(Transition)
60 in. (1524 mm)
66 in. (1676 mm)
72 in. (1829 mm)
78 in. (1981 mm)
84 in. (2134 mm)
90 in. (2286 mm)
475 (216)
500 (227)
525 (239)
550 (250)
575 (261)
600 (273)
22-in. (559 mm)
(Transition)
60 in. (1524 mm)
66 in. (1676 mm)
72 in. (1829 mm)
78 in. (1981 mm)
84 in. (2134 mm)
90 in. (2286 mm)
950 (432)
1000 (455)
1050 (477)
1100 (500)
1150 (523)
1200 (545)
Table A10 – Magnum DS Breaker Weights – Pounds (Kilograms)
➀
Breaker
Fixed
Drawout
MDS-408
MDS-608
MDS-808
MDS-C08
MDS-616
MDS-816
MDS-C16
MDS-620
MDS-820
MDS-C20
MDS-632
MDS-832
MDS-C32
MDS-840
MDS-C40
MDS-850
MDS-C50
110 (50)
110 (50)
120 (55)
120 (55)
110 (50)
120 (55)
120 (55)
120 (55)
120 (55)
120 (55)
135 (61)
135 (61)
135 (61)
250 (114)
250 (114)
250 (114)
250 (114)
130 (59)
130 (59)
145 (66)
145 (66)
130 (59)
145 (66)
145 (66)
145 (66)
145 (66)
145 (66)
175 (80)
175 (80)
175 (80)
310 (141)
310 (141)
310 (141)
310 (141)
➀
Manually or electrically operated. For
approximate impact weight, add 50% of
breaker weight.
➁
Contact Cutler-Hammer.
➂
For lower than maximum load currents, watt
loss may be estimated by reducing the full
load loss by the following:
W
L
= (I
L
/I
FL
)
2
W
FL
Where:
W
L
= Load Watts
W
FL
= Full Load Watts
I
L
= Actual Load Current
I
FL
= Full Load Current