background image

Technical Data

Effective:  May 1998

Page 

18

TD.44A.01.T.E

Cutler-Hammer

Ground Fault
When the sensing circuit detects a 
fault, the green “normal” light will turn 
off and the red “ground fault” light will 
turn on. The ground current ammeter 
will indicate the total ground current. 
To use the pulser, turn the system con-
trol switch to “pulse.” The pulser con-
tactor will cycle on and off as control-
led by the recycle timer relay. Use the 
clamp-on ammeter to locate the 
faulted feeder. Open the feeder and 
clear the fault. If the reset control 
switch is in the “manual” position, 
turn it to “reset” to reset the sensing 
circuit. (If reset control is in “auto,” it 
will reset itself.) When ready to restore 
service to the load, close the feeder. 
Return the system control to “normal.”

Zone Selective Interlocking
By definition, a selectively coordinated 
system is one where by adjusting trip 
unit pickup and time delay settings, the 
circuit breaker closest to the fault trips 
first. The upstream breaker serves two 
functions: 

1. Back-up protection to the down-

stream breaker and 

2. Protection of the conductors 

between the upstream and down-
stream breakers. These elements 
are provided for on Digitrip trip 
units.

For faults that occur on the conductors 
between the upstream and down-
stream breakers it is ideally desirable 
for the upstream breaker to trip with 
no time delay. This is the feature pro-
vided by zone selective interlocking. 
Digitrip trip units may be specified to 
utilize this option.

Zone selective interlocking is a com-
munication signal between trip units 
applied on upstream and downstream 
breakers. Each trip unit must be 
applied as if zone selective interlocking 
were not employed, and set for selec-
tive coordination.

Application note: 

It may not be possi-

ble to precisely locate faults within a 
conduit. The ground current may 
divide into many components, 
depending on the number of cables 
per phase, number of conduits per 
feeder, and the number and resistance 
of each ground point along the con-
duits. The resulting currents may be 
too small to allow detection, or may 
take a path that the ammeter cannot 
trace. An important note to keep in 
mind is that while the pulser can 
greatly aid in locating a fault, there 
may be certain conditions under which 
the pulses cannot be readily traced, 
and other test procedures (meg-ohm, 
high-potential, etc.) may be needed.

Sequence of Operation

Normal
Green “normal” light on.
Red “ground fault” light off.
White “pulse” light off.
System control switch in “normal” 
position.
Reset control switch in either “auto” or 
“manual.”

Test
Turn and hold the system control 
switch in the “test” position. Phase B 
will be grounded via the test resistor. 
The ground current will activate the 
sensing circuit, causing the green 
“normal” light to turn off and the red 
“ground fault” light to turn on. The 
pulser will be activated as well. The 
white “pulse” light will turn on and off 
as the pulser contactor closes and 
opens. The ground current ammeter 
will display the total ground current, 
including the incremental pulse cur-
rent. When ready, return the system 
control switch to “normal.” The pulser 
will stop. If the reset control is in the 
“manual” position, turn it to “reset” to 
reset the fault sensing circuit. The red 
“ground fault” light will turn off, and 
the green “normal” light will turn on. 
Test mode is not available if the sys-
tem is detecting a ground. The sensing 
circuit will disable the test circuit.

During fault conditions, each trip unit 
that senses the fault sends a restrain-
ing signal to all upstream trip units. 
This restraining signal results in caus-
ing the upstream trip to continue tim-
ing as it is set. In the absence of a 
restraining signal, the trip unit trips the 
associated breaker with no intentional 
time delay, minimizing damage to the 
fault point. This restraining signal is a 
very low level. To minimize the poten-
tial for induced noise, and to provide a 
low impedance interface between trip 
units, special twisted pair conductors 
are utilized for interconnection. For this 
reason, zone selective interlocking 
must be specified. 

Ground fault and short delay pickup on 
Digitrip Trip Units may be specified 
with zone selective interlocking. Since 
most system faults start as arcing 
ground faults, zone selective interlock-
ing on ground fault pickup only is 
usually adequate. Zone selective inter-
locking on short delay pickup may be 
utilized where no ground fault protec-
tion is provided.

Zone selective interlocking may be 
applied as a type of bus differential 
protection. It must be recognized, how-
ever, that one must accept the mini-
mum pickup of the trip unit for 
sensitivity.

It must also be recognized that not all 
systems may be equipped with zone 
selective Interlocking. Systems contain-
ing multiple sources, or where the direc-
tion of power flow varies, require special 
considerations, or may not be suitable 
for this feature. Digitrip zone interlocking 
has been tested with up to three levels 
with up to 20 trip units per level.

Magnum DS 
Metal-Enclosed 
Low-Voltage Switchgear

Application

www 

. ElectricalPartManuals 

. com 

Summary of Contents for Magnum DS

Page 1: ...nical Data Effective May 1998 Page 1 TD 44A 01 T E Cutler Hammer Magnum DS Metal Enclosed Low Voltage Switchgear New Information Mailed to E C 32 000B w w w E l e c t r i c a l P a r t M a n u a l s c...

Page 2: ...and 200 kA short circuit bus bracing without preced ing current limiting fuses Optional metal barriers isolates the cable compartment from the bus compartment Many other features for coordinated safe...

Page 3: ...as been tested for short circuit values of 85 000 amperes for a full 60 cycles Table R3 Standards Magnum DS switchgear conforms to the following standards NEMA SG3 and SG5 CSA ANSI C37 20 1 C37 51 and...

Page 4: ...otection In addition short delay protection may be set to the maximum instantaneous level effectively disabling short delay pro tection if instantaneous protection is turned off Under no condition is...

Page 5: ...400 400 1 25 1 50 1 75 2 00 2 50 3 00 3 75 5 00 600 600 1 25 1 50 1 75 2 00 2 50 3 00 3 75 5 00 800 800 1 25 1 50 1 75 2 00 2 50 3 00 3 75 5 00 1000 1000 1 25 1 50 1 75 2 00 2 50 3 00 3 75 5 00 1200...

Page 6: ...int indicated by rapid flashing of unit status LED on the product nominal occurs at 110 of the lr current with a 5 tolerance The short delay settings have conventional 100 5 as the pickup points 5 Wit...

Page 7: ...ing Plug ln 5 The instantaneous settings have conventional 100 10 as the pickup points 6 For additional curve tolerances contact Cutler Hammer 7 Total clearing times shown include the response times o...

Page 8: ...he rating plug is for 50 Hz and 60 Hz applications 8 Curves apply from 20 C to 50 C ambient temperatures above 95 C cause automatic trip 9 With zone interlocking on ground fault utilized and no restra...

Page 9: ...3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 6 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 6 0 6 0 3 0 3 0 3 0 3 0 3 0 3 1 2 0 6 0 6 0 3 0 3 0 3 0 3 0 3 4000 4000 5 4000 1 0 3 0 3 0 3 0 3 0 3 5000 5000 5 5000 1 Refe...

Page 10: ...a clean dry room with filtered and or pressurized clean air This method permits the use of standard indoor switchgear and avoids the derating effect of non ventilated enclosures 3 Salt spray excessiv...

Page 11: ...mmable types of transformers eliminates necessity of vaults Efficient space utilization Advantages of Magnum DS Unit Substations Complete coordination both mechanical and electrical Extreme flexibilit...

Page 12: ...ar to those on radial unit substations If required and equipped with the appropriate relaying either trans former can be removed from service and isolated with no interruption of service on either bus...

Page 13: ...ith down stream devices Maximum capabilities of transformers of various types in terms of kVA and secondary current are given in Tables A1 through A4 It will be noted that the maximum ratings will oft...

Page 14: ...otors Contactors are recom mended for this application when there are a number of daily operations involved When system short circuits are less than 40 times the motor full load current the motor brea...

Page 15: ...ounded but in some very rare cases it is grounded at one corner of the delta or at some other point When the source is wye connected it can be grounded or ungrounded and when grounded the grounding is...

Page 16: ...solid state trip unit is in addition to the usual phase protection The ground element has adjustable pickup with calibrated marks as shown in Tables R8 and R9 and adjustable time delay The input curr...

Page 17: ...r equipment main tenance and hence reduce the occur rence of unplanned shutdowns Indication and Alarm Circuits When a fault is detected an adjustable time delay is provided to override tran sients Whe...

Page 18: ...hite pulse light off System control switch in normal position Reset control switch in either auto or manual Test Turn and hold the system control switch in the test position Phase B will be grounded v...

Page 19: ...formers HV 600 Max Delta To Distribution Equipment C B A 3 2 1 AM 51N Pulser Resistor Grounding Resistor G High Resistance Grounding Assembly Test Resistor Control Circuit CLF CLF CLF G R W Artificial...

Page 20: ...nded 20 20 Standard resid ual ground pro tection for single source systems and source ground per SK 5 for multiple ground sources Mini mum pickup 0 50 sec time delay Ground 3 wire or 4 wire as require...

Page 21: ...type of application Cutler Ham mer should be consulted for the actual bill of materials to be used The appli cation becomes rather complex if sin gle phase to neutral loads are being served X X N1 C B...

Page 22: ...Trip Unit GF Trip Unit GF Trip Unit 0 22 Sec 0 22 Sec 0 50 Sec 0 35 Sec GF Trip Unit TIE 52 1 52 T Bus 1 52 2 Bus 2 Bus 2 Neutral Connection Bus 1 Neutral Connection 52 T 33T 52 T Typical Feeder Thes...

Page 23: ...DS 608 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 1000 5 75 2778 50000 100000 150000 250000 500000 Unlimited 35900 41200 43300 45200 46700 48300 5600 41500 46800 48900 50800 52300 53900 MDS 632 M...

Page 24: ...DS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 1500 5 75 1804 50000 100000 150000 250000 500000 Unlimited 20600 24900 26700 28400 29800 31400 7200 27800 32100 33900 356...

Page 25: ...08 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 1500 5 75 1443 50000 100000 150000 250000 500000 Unlimited 16500 20000 21400 22700 23900 25100 5800 22300 25800 27200 28500 2...

Page 26: ...eder 800 1600 2000 3200 Main 4000 5000 Main 4000 5000 Feeder 800 1600 2000 3200 Feeder 800 1600 2000 3200 Blank or Instrument 44 1118 Fig 6 44 1118 Fig 7 Maximum indoor shipping section width is 5 ver...

Page 27: ...Feeder 4000 5000 44 1118 Fig 11 44 1118 Fig 12 Maximum indoor shipping section width is 5 vertical sections or 120 inches 3048 mm whichever is smaller Maximum outdoor shipping width is 96 inches 2438...

Page 28: ...5000 Tie 4000 5000 Tie 4000 5000 Main 4000 5000 Feeder 800 1600 2000 3200 Feeder 800 1600 2000 3200 Blank or Instrument 44 1118 Fig 18 44 1118 Fig 19 Maximum indoor shipping section width is 5 vertic...

Page 29: ...ansformer connections etc All vertical sections are 92 inches 2339 mm high plus 4 inches 102 mm for ventilators and non removable lifting angle When a top of gear breaker lifter is used height is 99 i...

Page 30: ...izontal Cross Bus Area Vertical Bus Riser Area Lifting Plate Metal Enclosed Shipping Split Terminal Blocks Optional top of gear Breaker Lifter Magnum DS Metal Enclosed Low Voltage Switchgear Applicati...

Page 31: ...eft to right center of lineup From the front 26 inches 660 mm FC is the recommended front clearance for breaker removal with top of switchgear mounted breaker lifter If a portable breaker lifter is to...

Page 32: ...in 1829 mm 78 in 1981 mm 84 in 2134 mm 90 in 2286 mm 950 432 1000 455 1050 477 1100 500 1150 523 1200 545 11 in 279 mm Transition 60 in 1524 mm 66 in 1676 mm 72 in 1829 mm 78 in 1981 mm 84 in 2134 mm...

Page 33: ...ce interlocks are supplied on breakers and in compartments where the compartments are of the same physical size to assure an incorrect breaker cannot be inserted Key Interlock Switchgear Mounted Break...

Page 34: ...00 of main bus rating as standard Half 50 neu trals and neutral ratings up to a maxi mum of 6000 amperes are available as an option Ground A ground bus is furnished the full length of the switchgear a...

Page 35: ...cuit breaker The termi nal blocks are rated 30 amperes and will accept bare wire ring or spade ter minals for wire size ranges of 22 to 10 Extruded loops are punched in side sheets of the vertical wir...

Page 36: ...ndary Terminal Compartment Door Devices such as control push buttons breaker control switches indi cating lights and test switches can be mounted on these panels within space limitations The ammeters...

Page 37: ...he breaker closing springs are charged either through the manual charging handle or by the optional charging motor The breaker is mechanically interlocked to prevent closing of the breaker until the c...

Page 38: ...n the breaker Optional Breaker Attachments and Accessories a Shunt trip on manually operated breakers for any standard control voltage b Auxiliary contacts on manually or electrically operated breaker...

Page 39: ...CNC C5 CNO C11 CNO B30 B29 M M C7 C8 C10 C9 CNC CNO CNC B15 B14 C1 C2 C4 C3 C12 CNO C6 Breaker Auxiliary Contacts Shown with Breaker in Open Position Breaker Auxiliary Contacts Shown with Breaker in...

Page 40: ...tilize Belleville type spring washers to main tain maximum joint integrity through continuous thermal cycling The bus system shall be suitable for applica tions on power systems requiring a 100 150 20...

Page 41: ...y means of a portable plug in test device Both electrically operated and manu ally operated breakers shall have stored energy operating mechanisms The device to close the breaker shall be by means of...

Page 42: ...Technical Data Effective May 1998 Page 42 TD 44A 01 T E Cutler Hammer w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 43: ...Technical Data Effective May 1998 Page 43 TD 44A 01 T E Cutler Hammer w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 44: ...echnical Data Effective May 1998 Page 44 TD 44A 01 T E Printed in U S A Cutler Hammer Cutler Hammer Magnum DS Metal Enclosed Low Voltage Switchgear w w w E l e c t r i c a l P a r t M a n u a l s c o...

Reviews: