background image

Technical Data

Effective:  May 1998

Page 

13

TD.44A.01.T.E

Cutler-Hammer

Magnum DS 
Metal-Enclosed 
Low-Voltage Switchgear

Application

System Application
Most Magnum DS

 

Switchgear is fed 

from power transformers. To facilitate 
minimum breaker sizing, Tables A1 
through A4 Iists the calculated second-
ary short circuit currents and applica-
ble main secondary and feeder 
breakers for various transformer sizes 
and voltages.

The short circuit currents are calculated 
by dividing the transformer basic 
(100%) rated amperes by the sum of the 
transformer and primary system imped-
ances, expressed in “per unit.” The 
transformer impedance percentages are 
standard for most secondary unit sub-
station transformers. The primary 
impedance is obtained by dividing the 
transformer base (100%) kVA by the pri-
mary short circuit kVA. The motor con-
tributions to the short circuit currents 
are estimated as approximately 4 times 
the motor load amperes, which in turn 
are based upon 50% of the total load for 
208 system voltages and 100% for all 
other voltages.

High transformer impedances and/or 
lower percentages of motor loads will 
reduce the short circuit currents corre-
spondingly. Supplementary trans-
former cooling and temperature 
ratings will not increase the short cir-
cuit currents, provided the motor loads 
are not increased.

The tables do not apply for 3-phase 
banks of single-phase distribution 
transformers, which usually have 
impedances of 2% to 3% or even lower. 
The short circuit currents must be 
recalculated for all such applications, 
and the breakers selected accordingly.

Transformer Main Secondary Breakers
Transformer secondary breakers are 
required or recommended for one or 
more of the following purposes:

1. To provide a one-step means of 

removing all load from the trans-
former.

2. To provide transformer overload 

protection in the absence of an indi-
vidual primary breaker, and/or when 
primary fuses are used.

3. To provide the fastest clearing of 

a short circuit in the secondary 
main bus.

4. To provide a local disconnecting 

means, in the absence of a local pri-
mary switch or breaker, for mainte-
nance purposes.

5. For automatic or manual transfer 

of loads to alternate sources, as in 
double-ended secondary selective 
unit substations.

6. For simplifying key interlocking with 

primary interrupter switches.

7. To satisfy NEC service entrance 

requirements when more than six 
feeder breakers are required.

Main secondary breakers, as selected 
in Tables A1 through A4, have ade-
quate interrupting ratings, but not nec-
essarily adequate continuous current 
ratings. They should be able to carry 
continuously not only the anticipated 
maximum continuous output of the 
transformer but also any temporary 
overloads.

For a fully selective system, instanta-
neous protection on main breakers 
should be defeated, as they typically 
cannot be coordinated with down-
stream devices.

Maximum capabilities of transformers 
of various types, in terms of kVA and 
secondary current, are given in Tables 
A1 through A4. It will be noted that the 
maximum ratings will often require the 
substitution of larger frame main 
breakers than those listed in the tables. 
Even if a self-cooled transformer only 
is considered, it should be remem-
bered that with ratings of 750 kVA and 
higher, provision for the future addi-
tion of cooling fans is automatically 
included. It is recommended that the 
main breaker have sufficient capacity 
for the future fan-cooled rating, plus an 
allowance for overloads, if possible, 
particularly since load growth cannot 
always be predicted.

The same considerations should be 
given to the main bus capacities and 
main current transformer ratios.

Bus Sectionalizing (Tie) Breakers
The minimum recommended continu-
ous current rating of bus sectionalizing 
or tie breakers, as used in double-
ended secondary selective unit 

substations, or for connecting two sin-
gle-ended substations, is one-half that 
of the associated main breakers. The 
interrupting rating should be at least 
equal to that of the feeder breakers. It 
is common practice to select the tie 
breaker of the next frame size below 
that of the main breakers. However, 
many users and engineers prefer that 
the tie breaker be identical to and inter-
changeable with the main breakers, so 
that under normal conditions it will be 
available as a spare main breaker.

In general, the tie breaker, like the main 
breaker, trip unit should have its 
instantaneous tripping defeated.

Generator Breakers
In most applications where generators 
are connected through breakers to the 
secondary bus, they are used as emer-
gency standby sources only, and are 
not synchronized or paralleled with the 
unit substation transformers. Under 
these conditions, the interrupting rat-
ing of the generator breaker will be 
based solely on the generator kVA and 
sub-transient reactance. This reactance 
varies with the generator type and 
rpm, from a minimum of approxi-
mately 9% for a 2-pole 3600 rpm tur-
bine driven generator to 15% or 20% or 
more for a medium or slow speed 
engine type generator. Thus the feeder 
breakers selected for the unit substa-
tion will usually be adequate for a 
standby generator of the same kVA as 
the transformer.

Most generators have a 2-hour 25% 
overload rating, and the generator 
breaker must be adequate for this 
overload current. Selective type long 
and short delay trip protection only is 
usually recommended for coordination 
with the feeder breakers, with the long 
delay elements set at 125% to 150% of 
the maximum generator current rating 
for generator protection.

In the case of two or more paralleled 
generators, anti-motoring reverse 
power relays (device 32) are recom-
mended for protection of the prime 
movers, particularly piston type 
engines. For larger generators requir-
ing a Magnum MDS-632 or larger, volt-
age-restraint type overcurrent relays 
(device 51V) are recommended.

www 

. ElectricalPartManuals 

. com 

Summary of Contents for Magnum DS

Page 1: ...nical Data Effective May 1998 Page 1 TD 44A 01 T E Cutler Hammer Magnum DS Metal Enclosed Low Voltage Switchgear New Information Mailed to E C 32 000B w w w E l e c t r i c a l P a r t M a n u a l s c...

Page 2: ...and 200 kA short circuit bus bracing without preced ing current limiting fuses Optional metal barriers isolates the cable compartment from the bus compartment Many other features for coordinated safe...

Page 3: ...as been tested for short circuit values of 85 000 amperes for a full 60 cycles Table R3 Standards Magnum DS switchgear conforms to the following standards NEMA SG3 and SG5 CSA ANSI C37 20 1 C37 51 and...

Page 4: ...otection In addition short delay protection may be set to the maximum instantaneous level effectively disabling short delay pro tection if instantaneous protection is turned off Under no condition is...

Page 5: ...400 400 1 25 1 50 1 75 2 00 2 50 3 00 3 75 5 00 600 600 1 25 1 50 1 75 2 00 2 50 3 00 3 75 5 00 800 800 1 25 1 50 1 75 2 00 2 50 3 00 3 75 5 00 1000 1000 1 25 1 50 1 75 2 00 2 50 3 00 3 75 5 00 1200...

Page 6: ...int indicated by rapid flashing of unit status LED on the product nominal occurs at 110 of the lr current with a 5 tolerance The short delay settings have conventional 100 5 as the pickup points 5 Wit...

Page 7: ...ing Plug ln 5 The instantaneous settings have conventional 100 10 as the pickup points 6 For additional curve tolerances contact Cutler Hammer 7 Total clearing times shown include the response times o...

Page 8: ...he rating plug is for 50 Hz and 60 Hz applications 8 Curves apply from 20 C to 50 C ambient temperatures above 95 C cause automatic trip 9 With zone interlocking on ground fault utilized and no restra...

Page 9: ...3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 6 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 6 0 6 0 3 0 3 0 3 0 3 0 3 0 3 1 2 0 6 0 6 0 3 0 3 0 3 0 3 0 3 4000 4000 5 4000 1 0 3 0 3 0 3 0 3 0 3 5000 5000 5 5000 1 Refe...

Page 10: ...a clean dry room with filtered and or pressurized clean air This method permits the use of standard indoor switchgear and avoids the derating effect of non ventilated enclosures 3 Salt spray excessiv...

Page 11: ...mmable types of transformers eliminates necessity of vaults Efficient space utilization Advantages of Magnum DS Unit Substations Complete coordination both mechanical and electrical Extreme flexibilit...

Page 12: ...ar to those on radial unit substations If required and equipped with the appropriate relaying either trans former can be removed from service and isolated with no interruption of service on either bus...

Page 13: ...ith down stream devices Maximum capabilities of transformers of various types in terms of kVA and secondary current are given in Tables A1 through A4 It will be noted that the maximum ratings will oft...

Page 14: ...otors Contactors are recom mended for this application when there are a number of daily operations involved When system short circuits are less than 40 times the motor full load current the motor brea...

Page 15: ...ounded but in some very rare cases it is grounded at one corner of the delta or at some other point When the source is wye connected it can be grounded or ungrounded and when grounded the grounding is...

Page 16: ...solid state trip unit is in addition to the usual phase protection The ground element has adjustable pickup with calibrated marks as shown in Tables R8 and R9 and adjustable time delay The input curr...

Page 17: ...r equipment main tenance and hence reduce the occur rence of unplanned shutdowns Indication and Alarm Circuits When a fault is detected an adjustable time delay is provided to override tran sients Whe...

Page 18: ...hite pulse light off System control switch in normal position Reset control switch in either auto or manual Test Turn and hold the system control switch in the test position Phase B will be grounded v...

Page 19: ...formers HV 600 Max Delta To Distribution Equipment C B A 3 2 1 AM 51N Pulser Resistor Grounding Resistor G High Resistance Grounding Assembly Test Resistor Control Circuit CLF CLF CLF G R W Artificial...

Page 20: ...nded 20 20 Standard resid ual ground pro tection for single source systems and source ground per SK 5 for multiple ground sources Mini mum pickup 0 50 sec time delay Ground 3 wire or 4 wire as require...

Page 21: ...type of application Cutler Ham mer should be consulted for the actual bill of materials to be used The appli cation becomes rather complex if sin gle phase to neutral loads are being served X X N1 C B...

Page 22: ...Trip Unit GF Trip Unit GF Trip Unit 0 22 Sec 0 22 Sec 0 50 Sec 0 35 Sec GF Trip Unit TIE 52 1 52 T Bus 1 52 2 Bus 2 Bus 2 Neutral Connection Bus 1 Neutral Connection 52 T 33T 52 T Typical Feeder Thes...

Page 23: ...DS 608 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 1000 5 75 2778 50000 100000 150000 250000 500000 Unlimited 35900 41200 43300 45200 46700 48300 5600 41500 46800 48900 50800 52300 53900 MDS 632 M...

Page 24: ...DS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 1500 5 75 1804 50000 100000 150000 250000 500000 Unlimited 20600 24900 26700 28400 29800 31400 7200 27800 32100 33900 356...

Page 25: ...08 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 MDS 408 1500 5 75 1443 50000 100000 150000 250000 500000 Unlimited 16500 20000 21400 22700 23900 25100 5800 22300 25800 27200 28500 2...

Page 26: ...eder 800 1600 2000 3200 Main 4000 5000 Main 4000 5000 Feeder 800 1600 2000 3200 Feeder 800 1600 2000 3200 Blank or Instrument 44 1118 Fig 6 44 1118 Fig 7 Maximum indoor shipping section width is 5 ver...

Page 27: ...Feeder 4000 5000 44 1118 Fig 11 44 1118 Fig 12 Maximum indoor shipping section width is 5 vertical sections or 120 inches 3048 mm whichever is smaller Maximum outdoor shipping width is 96 inches 2438...

Page 28: ...5000 Tie 4000 5000 Tie 4000 5000 Main 4000 5000 Feeder 800 1600 2000 3200 Feeder 800 1600 2000 3200 Blank or Instrument 44 1118 Fig 18 44 1118 Fig 19 Maximum indoor shipping section width is 5 vertic...

Page 29: ...ansformer connections etc All vertical sections are 92 inches 2339 mm high plus 4 inches 102 mm for ventilators and non removable lifting angle When a top of gear breaker lifter is used height is 99 i...

Page 30: ...izontal Cross Bus Area Vertical Bus Riser Area Lifting Plate Metal Enclosed Shipping Split Terminal Blocks Optional top of gear Breaker Lifter Magnum DS Metal Enclosed Low Voltage Switchgear Applicati...

Page 31: ...eft to right center of lineup From the front 26 inches 660 mm FC is the recommended front clearance for breaker removal with top of switchgear mounted breaker lifter If a portable breaker lifter is to...

Page 32: ...in 1829 mm 78 in 1981 mm 84 in 2134 mm 90 in 2286 mm 950 432 1000 455 1050 477 1100 500 1150 523 1200 545 11 in 279 mm Transition 60 in 1524 mm 66 in 1676 mm 72 in 1829 mm 78 in 1981 mm 84 in 2134 mm...

Page 33: ...ce interlocks are supplied on breakers and in compartments where the compartments are of the same physical size to assure an incorrect breaker cannot be inserted Key Interlock Switchgear Mounted Break...

Page 34: ...00 of main bus rating as standard Half 50 neu trals and neutral ratings up to a maxi mum of 6000 amperes are available as an option Ground A ground bus is furnished the full length of the switchgear a...

Page 35: ...cuit breaker The termi nal blocks are rated 30 amperes and will accept bare wire ring or spade ter minals for wire size ranges of 22 to 10 Extruded loops are punched in side sheets of the vertical wir...

Page 36: ...ndary Terminal Compartment Door Devices such as control push buttons breaker control switches indi cating lights and test switches can be mounted on these panels within space limitations The ammeters...

Page 37: ...he breaker closing springs are charged either through the manual charging handle or by the optional charging motor The breaker is mechanically interlocked to prevent closing of the breaker until the c...

Page 38: ...n the breaker Optional Breaker Attachments and Accessories a Shunt trip on manually operated breakers for any standard control voltage b Auxiliary contacts on manually or electrically operated breaker...

Page 39: ...CNC C5 CNO C11 CNO B30 B29 M M C7 C8 C10 C9 CNC CNO CNC B15 B14 C1 C2 C4 C3 C12 CNO C6 Breaker Auxiliary Contacts Shown with Breaker in Open Position Breaker Auxiliary Contacts Shown with Breaker in...

Page 40: ...tilize Belleville type spring washers to main tain maximum joint integrity through continuous thermal cycling The bus system shall be suitable for applica tions on power systems requiring a 100 150 20...

Page 41: ...y means of a portable plug in test device Both electrically operated and manu ally operated breakers shall have stored energy operating mechanisms The device to close the breaker shall be by means of...

Page 42: ...Technical Data Effective May 1998 Page 42 TD 44A 01 T E Cutler Hammer w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 43: ...Technical Data Effective May 1998 Page 43 TD 44A 01 T E Cutler Hammer w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 44: ...echnical Data Effective May 1998 Page 44 TD 44A 01 T E Printed in U S A Cutler Hammer Cutler Hammer Magnum DS Metal Enclosed Low Voltage Switchgear w w w E l e c t r i c a l P a r t M a n u a l s c o...

Reviews: